Permit #2025100717
Permit Details
Status: INSPECT
| Parcel Id: 04-11-30-5571-00000-3420 |
| CONDITIONED SPACE: 1638 sqft |
| GARAGE: 461 sqft |
| OPENED PORCH (WITH ROOF) : 96 sqft |
| OPENED PORCH (WITH ROOF) : 112 sqft |
| Total Square Footage: 2307 sqft |
| Subdivision: 2366 - SOMERSET SUBDIVISION PH 2 |
| Job Phone: 904-596-6645 |
| Location Address: 53 SOMERSET AVE |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 12/23/2025 |
| NOC: RECORDED |
| Applicant name: MICHAEL T HOLDER |
| Owner: KB HOME JACKSONVILLE LLC |
|
Address 10475 FORTUNE PARKWAY JACKSONVILLE, FL 32256 |
|
Address SUITE 100 JACKSONVILLE, FL 32256 |
| Lot: 342 |
| Contracted Stated Job Value: ¤140,000.00 |
| Job Description: NEW SINGLE FAMILY DWELLING |
| Type: CN |
Contractor
KB HOME JACKSONVILLE, LLC
| Status | Location Address | Mailing Address | State License Number | Phone |
| ACTIVE |
10475 FORTUNE PKWY JACKSONVILLE, FL 32256 |
SUITE 100 JACKSONVILLE, FL 32256 |
CGC1509034 (Exp: 08/31/2026) | 904-596-6645 |
Sub Contractors
BOBBY WAYNE CAMPBELL
| Status | Location Address | State License Number | Phone |
| ACTIVE |
117 GUTHRIE ROAD GREEN COVE SPRINGS, FL 32043 |
CCC1326752 (Exp: 08/31/2026) | 904-200-1600 |
COREY MICHAEL TENNANT
| Status | Location Address | State License Number | Phone |
| ACTIVE |
3370 AGRICULTURAL CNETER DR ST AUGUSTINE, FL 32092 |
CAC1819063 (Exp: 08/31/2026) | 904-829-8898 |
JAMES E LINTON
| Status | Location Address | State License Number | Phone |
| ACTIVE |
200 COLLEGE DR ORANGE PARK, FL 32065 |
EC0001152 (Exp: 08/31/2026) | 904-272-0272 |
BENJAMIN MICHAEL RAY
| Status | Location Address | Mailing Address | State License Number | Phone | Fax |
| ACTIVE |
6310 MABLETON PKWY JACKSONVILLE, FL 32216 |
SUITE 1000 MABLETON, GA 30126 |
CFC1428415 (Exp: 08/31/2026) | 904-861-5421 | 904-861-5426 |
LARRY WILLIAMS
| Status | Location Address | State License Number | Phone |
| ACTIVE |
1750 EMERSON ST JACKSONVILLE, FL 32207 |
LI45034 (Exp: 08/31/2026) | 904-721-5431 |
Inspection History
| Type | Request Date | Result | Inspector |
| ROW- PROJECT STATUS | 05/14/2026 | APPROVED - AS NOTED | RRICKS |
| Note: 5/14/2026 - RRicks Gabriel and I conducted a site visit and there is severe erosion on 49,51, and 53 where the ground was disturbed and new sod was installed. Please make all necessary corrections as soon as possible. | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 05/14/2026 | Disapproved - NO FEE | RRICKS |
| Note: 5/14/2026 - RRicks Checklist Item 23: As discussed with Fidel and Scott, the approved master plan and the approved grading plan have this lot as an A-type NOT a B-type. Gabriel and I conducted a site visit and there is severe erosion on 49,51, and 53 where the ground was disturbed and new sod was installed. Please make all necessary corrections as soon as possible. | |||
| BLD - BUILDING FINAL | 03/19/2026 | FINAL APPROVED | JSTEWART |
| Note: 3/16/2026 - PREVIOUS INSPECTION NOTES 1. Loose locking caps on outside unit. FBCR M1411.8 2. Garage door inoperable. 3. No hot water. 4. Missing weather striping in front door. 5. Missing insulation certificate. FBC EC R303.1.1.2 | |||
| U-CROSS CONNECTION | 03/16/2026 | APPROVED - AS NOTED | BVEIGA |
| Note: No CC. IRR with reuse water. | |||
| BLD - BUILDING FINAL | 03/16/2026 | Disapproved - NO FEE | PKNAPIK |
| Note: 1. Loose locking caps on outside unit. FBCR M1411.8 2. Garage door inoperable. 3. No hot water. 4. Missing weather striping in front door. 5. Missing insulation certificate. FBC EC R303.1.1.2 | |||
| ELECTRIC - EARLY POWER | 02/27/2026 | APPROVED | KSANDOE |
| Note: Inspector Notes from Inspection 2200 Authorize release of email. | |||
| ROW- PRE-APRON (PRE-POUR) | 02/10/2026 | APPROVED | TPOLACEK |
| Note: AT THE TIME OF THE INSPECTION READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK ELEVATIONS MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL BEFORE POURING. . TICKET OF CONCRETE MIX DESIGN SHALL BE UPLOADED INTO PERMIT PORTAL. 8.a. IF FIBERGLASS OPTION IS USED, IN THE UPCOMING MONTHS THE DOCUMENTATION OF THE ( FRC) CONTAINING THE FIBERGLASS WILL BE REQUIRED TO BE ATTACHED TO THE PERMIT PRIOR TO REQUESTING AN AFTER-POUR INSPECTION. YOU WILL RECEIVE A NEWS BLAST WHEN THIS BECOMES NECESSARY | |||
| INSULATION | 02/04/2026 | APPROVED | JSTEWART |
| Note: 2/3/2026 - PREVIOUS INSPECTION NOTES Previous Not not rectified......2. Hood exhaust duct is installed in reverse, please install where the male end at the laps are in the direction of flow. joints are required to lap min 1" and connected with 3 screws, lap in the direction of flow. (cannot butt the seams). Inspector Notes from Inspection 2420 *** NOTES ADDED BY JSTEWART 1/30/2026 10:37:23 AM *** disreguard note number 3. Pulled up wrong address. 1. Please re seal dryer duct roof penetration. FBCR M1601.4.1 / M1501.1 2. Hood exhaust duct is installed in reverse, please install where the male end at the laps are in the direction of flow. M1601.4.2 3. Please submit a revision of energy calcs for HVAC dust layout, (Added Trunk duct, and distribution Box). FBC (A) 107.4 Corrections prior to Insulation. | |||
| INSULATION | 02/03/2026 | Disapproved -FEE REQUIRED | JSTEWART |
| Note: Previous Not not rectified......2. Hood exhaust duct is installed in reverse, please install where the male end at the laps are in the direction of flow. joints are required to lap min 1" and connected with 3 screws, lap in the direction of flow. (cannot butt the seams). Inspector Notes from Inspection 2420 *** NOTES ADDED BY JSTEWART 1/30/2026 10:37:23 AM *** disreguard note number 3. Pulled up wrong address. 1. Please re seal dryer duct roof penetration. FBCR M1601.4.1 / M1501.1 2. Hood exhaust duct is installed in reverse, please install where the male end at the laps are in the direction of flow. M1601.4.2 3. Please submit a revision of energy calcs for HVAC dust layout, (Added Trunk duct, and distribution Box). FBC (A) 107.4 Corrections prior to Insulation. | |||
| LATH/BRICK/ WATER BARRIER | 02/03/2026 | APPROVED | JSTEWART |
| Note: Inspector Notes from Inspection 2420 *** NOTES ADDED BY JSTEWART 1/30/2026 10:37:23 AM *** disreguard note number 3. Pulled up wrong address. 1. Please re seal dryer duct roof penetration. FBCR M1601.4.1 / M1501.1 2. Hood exhaust duct is installed in reverse, please install where the male end at the laps are in the direction of flow. M1601.4.2 3. Please submit a revision of energy calcs for HVAC dust layout, (Added Trunk duct, and distribution Box). FBC (A) 107.4 Corrections prior to Insulation. | |||
| ALL ROUGH | 01/30/2026 | APPROVED - AS NOTED | JSTEWART |
| Note: *** NOTES ADDED BY JSTEWART 1/30/2026 10:37:23 AM *** disreguard note number 3. Pulled up wrong address. 1. Please re seal dryer duct roof penetration. FBCR M1601.4.1 / M1501.1 2. Hood exhaust duct is installed in reverse, please install where the male end at the laps are in the direction of flow. M1601.4.2 3. Please submit a revision of energy calcs for HVAC dust layout, (Added Trunk duct, and distribution Box). FBC (A) 107.4 Corrections prior to Insulation. | |||
| ELECTRIC-TUG | 01/30/2026 | APPROVED - AS NOTED | JSTEWART |
| Note: Authorize release of email. | |||
| ROOF VALLEY & METAL | 01/26/2026 | APPROVED | JSTEWART |
| Note: Inspector Notes from Inspection 2450 Prior dis approval was entered in error wrong address, sheathing is approved. 1/21/2026 - PREVIOUS INSPECTION NOTES Missing nails thruought. Nails need to be embedded (sticking out to far) Excessive shiners need to be removed and replaced. Inspector Notes from Inspection 2250 Return Inspection 2:05pm. Corrections completed, footer depths range from 26" to 28" from top of form boards. 1/8/2026 - PREVIOUS INSPECTION NOTES Footing needs to be deeper in undisturbed ground Min 25" from top of form board. evaluated from Grade and drainage plan submitted and approved of a FFE 39.10, and the Lowest point of finish grade is at 38.0, which would have 13.2" of foundation above grade, Footing requires a min of 12" below final Grade. Per plan / R403.1.4 Minimum depth. Previous was approved on accident wrong address. Inspection still required. | |||
| WALL SHEATHING | 01/21/2026 | Disapproved - NO FEE | JSTEWART |
| Note: *** NOTES ADDED BY JSTEWART 1/21/2026 2:59:06 PM *** disreguard previous notes entered wrong address. added inspection back and approved Missing nails thruought. Nails need to be embedded (sticking out to far) Excessive shiners need to be removed and replaced. Inspector Notes from Inspection 2250 Return Inspection 2:05pm. Corrections completed, footer depths range from 26" to 28" from top of form boards. 1/8/2026 - PREVIOUS INSPECTION NOTES Footing needs to be deeper in undisturbed ground Min 25" from top of form board. evaluated from Grade and drainage plan submitted and approved of a FFE 39.10, and the Lowest point of finish grade is at 38.0, which would have 13.2" of foundation above grade, Footing requires a min of 12" below final Grade. Per plan / R403.1.4 Minimum depth. | |||
| WALL SHEATHING | 01/21/2026 | APPROVED - AS NOTED | JSTEWART |
| Note: Prior dis approval was entered in error wrong address, sheathing is approved. 1/21/2026 - PREVIOUS INSPECTION NOTES Missing nails thruought. Nails need to be embedded (sticking out to far) Excessive shiners need to be removed and replaced. Inspector Notes from Inspection 2250 Return Inspection 2:05pm. Corrections completed, footer depths range from 26" to 28" from top of form boards. 1/8/2026 - PREVIOUS INSPECTION NOTES Footing needs to be deeper in undisturbed ground Min 25" from top of form board. evaluated from Grade and drainage plan submitted and approved of a FFE 39.10, and the Lowest point of finish grade is at 38.0, which would have 13.2" of foundation above grade, Footing requires a min of 12" below final Grade. Per plan / R403.1.4 Minimum depth. | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 01/21/2026 | APPROVED - AS NOTED | JSTEWART |
| Note: *** NOTES ADDED BY JSTEWART 1/21/2026 2:56:41 PM *** Disreguard previous notes entered on wrong address. Approved Missing Nails at dry bottoms front and back porch posts. Moving forward all clips and tie downs need to be nailed to the structural member if using short stub nails, if going thru sheathing will need to use 2" nails for proper embeddment. I spoke with framing super. Inspector Notes from Inspection 2250 Return Inspection 2:05pm. Corrections completed, footer depths range from 26" to 28" from top of form boards. 1/8/2026 - PREVIOUS INSPECTION NOTES Footing needs to be deeper in undisturbed ground Min 25" from top of form board. evaluated from Grade and drainage plan submitted and approved of a FFE 39.10, and the Lowest point of finish grade is at 38.0, which would have 13.2" of foundation above grade, Footing requires a min of 12" below final Grade. Per plan / R403.1.4 Minimum depth. | |||
| ROOF VALLEY & METAL | 01/21/2026 | APPROVED - AS NOTED | JSTEWART |
| Note: Please seal L flashing at roof to wall prior to lath/brick/water barrier Inspector Notes from Inspection 2250 Return Inspection 2:05pm. Corrections completed, footer depths range from 26" to 28" from top of form boards. 1/8/2026 - PREVIOUS INSPECTION NOTES Footing needs to be deeper in undisturbed ground Min 25" from top of form board. evaluated from Grade and drainage plan submitted and approved of a FFE 39.10, and the Lowest point of finish grade is at 38.0, which would have 13.2" of foundation above grade, Footing requires a min of 12" below final Grade. Per plan / R403.1.4 Minimum depth. | |||
| GRAVITY SEWER TEST | 01/20/2026 | APPROVED | JSTEWART |
| Note: *** NOTES ADDED BY JSTEWART 1/20/2026 11:37:22 AM *** Live virtual Inspector Notes from Inspection 2060 At time of inspection water supply has not been hooked up to utility, Notes from Building offical will be checked at mono inspection-"At the front of the home, the grade adjacent to the foundation on the right side shows a 1.1' drop from the finished floor. Please verify that this grade can be achieved while still maintaining the required 12" of footer burial" | |||
| SEWER TIE IN | 01/20/2026 | APPROVED | JSTEWART |
| Note: *** NOTES ADDED BY JSTEWART 1/20/2026 11:37:42 AM *** Live virtual Inspector Notes from Inspection 2060 At time of inspection water supply has not been hooked up to utility, Notes from Building offical will be checked at mono inspection-"At the front of the home, the grade adjacent to the foundation on the right side shows a 1.1' drop from the finished floor. Please verify that this grade can be achieved while still maintaining the required 12" of footer burial" | |||
| MONOLITHIC SLAB | 01/08/2026 | Disapproved - NO FEE | JSTEWART |
| Note: Footing needs to be deeper in undisturbed ground Min 25" from top of form board. evaluated from Grade and drainage plan submitted and approved of a FFE 39.10, and the Lowest point of finish grade is at 38.0, which would have 13.2" of foundation above grade, Footing requires a min of 12" below final Grade. Per plan / R403.1.4 Minimum depth. | |||
| MONOLITHIC SLAB | 01/08/2026 | APPROVED - AS NOTED | JSTEWART |
| Note: Return Inspection 2:05pm. Corrections completed, footer depths range from 26" to 28" from top of form boards. 1/8/2026 - PREVIOUS INSPECTION NOTES Footing needs to be deeper in undisturbed ground Min 25" from top of form board. evaluated from Grade and drainage plan submitted and approved of a FFE 39.10, and the Lowest point of finish grade is at 38.0, which would have 13.2" of foundation above grade, Footing requires a min of 12" below final Grade. Per plan / R403.1.4 Minimum depth. | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 12/31/2025 | APPROVED - AS NOTED | MKRASKI |
| Note: At time of inspection water supply has not been hooked up to utility, Notes from Building offical will be checked at mono inspection-"At the front of the home, the grade adjacent to the foundation on the right side shows a 1.1' drop from the finished floor. Please verify that this grade can be achieved while still maintaining the required 12" of footer burial" | |||
| WATER METER INSTALLATION REQUEST | 12/31/2025 | APPROVED | CBOWERMASTER |
| FORMBOARD SURVEY (OFFICE USE ONLY) | 12/29/2025 | APPROVED | RRICKS |
| ROW - FINAL APRON (AFTER POUR) | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | |||
| Note: 5/14/2026 9:02:55 AM- PREVIOUS INSPECTION NOTES 5/14/2026 - RRicks Checklist Item 23: As discussed with Fidel and Scott, the approved master plan and the approved grading plan have this lot as an A-type NOT a B-type. Gabriel and I conducted a site visit and there is severe erosion on 49,51, and 53 where the ground was disturbed and new sod was installed. Please make all necessary corrections as soon as possible. | |||
| ROW - FINAL INSPECTION | |||
| U -UTILITY RESIDENTIAL FINAL |
Review History
| Department | Status | Date In | Date Out |
| SW1 | COMPLETE | 12/26/2025 | 12/26/2025 |
| Note: Released By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 12/26/2025 | 12/26/2025 |
| Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM | |||
| SW1 | COMPLETE | 12/17/2025 | 12/22/2025 |
| Note: Released By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM Approved as noted: There is a proposed 1.1' grade drop at the front right side of this home from the finished floor. Please ensure this drop can be made and still meet the FBC requiring 12" of footer burial. Note 1: There is an approved modification 6508 increasing the FFEs of both lots. Approved grading plan does not reflect the modified FFEs. | |||
| SW1 | HOLD | 11/07/2025 | 11/12/2025 |
| Note: Held By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM After further conversations with Dennis Leap the City's Engineer. Please review all A-type lots with this same issue for this subdivision and submit modification for each. If there are any questions or concerns. Please call Dennis Leap 386-986-2482. | |||
| URB | COMPLETE | 10/21/2025 | 10/28/2025 |
| Note: Released By: JOHN BEAUDET - (386)986-2456 - JBEAUDET@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 10/20/2025 | 10/24/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| CUSVC | COMPLETE | 10/20/2025 | 10/27/2025 |
| Note: Released By: HALEIGH HAND - - HHAND@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 10/20/2025 | 10/24/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ENGIN1 | COMPLETE | 10/20/2025 | 10/21/2025 |
| Note: Released By: LEVI SALYERDS - (386)986-2575 - LSALYERDS@PALMCOASTGOV.COM | |||
| GAS | COMPLETE | 10/20/2025 | 10/21/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| LOCATE | COMPLETE | 10/20/2025 | 10/23/2025 |
| Note: Released By: CANDACE BOWERMASTER - - CBOWERMASTER@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 10/20/2025 | 10/21/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| SW1 | HOLD | 10/20/2025 | 10/23/2025 |
| Note: Held By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM Grading Plan Comments: - Please provide an engineer's letter explaining why the deviation from the approved master plan is needed. - There shall be a minimum of 0.3' from the back of the lot to the rear yard drainage swale so the water flow to the front of this lot as designed. | |||
| ZON | COMPLETE | 10/20/2025 | 10/22/2025 |
| Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| FC IMPACT FEE EMS | ¤62.00 | 12/23/2025 |
| FC IMPACT FEE LAW ENFORCEMENT | ¤218.00 | 12/23/2025 |
| FC IMPACT FEE LIBRARY | ¤268.00 | 12/23/2025 |
| FIRE RES IMPACT FEE 10-25 | ¤942.00 | 12/23/2025 |
| WATER METER W/OUT TAP | ¤965.03 | 12/23/2025 |
| PARKS IMPACT FEE 10-25 | ¤3,164.00 | 12/23/2025 |
| RECLAIM WATER PERMIT INSPECTIO | ¤40.00 | 12/23/2025 |
| RSI DRIVEWAY AFTER POUR | ¤16.25 | 12/23/2025 |
| RSE DRIVE PRE POUR INSPECTION | ¤32.50 | 12/23/2025 |
| RSI FIELD SURVEY INSPECTION | ¤48.75 | 12/23/2025 |
| RSI FORMBOARD REVIEW | ¤16.25 | 12/23/2025 |
| RSI PLAN REVIEW NEW | ¤48.75 | 12/23/2025 |
| RSI FNL SURVEY/GRADING CERT | ¤48.75 | 12/23/2025 |
| RSI ROW FINAL INSPECTION | ¤16.25 | 12/23/2025 |
| SCHOOL BOARD IMPACT FEE RES | ¤5,450.00 | 12/23/2025 |
| SURCHARGE FS 533.721 | ¤11.84 | 12/23/2025 |
| SURCHARGE - FS 468.631 | ¤17.77 | 12/23/2025 |
| TRANSP RES IMPACT FEE 10-25 | ¤6,175.26 | 12/23/2025 |
| WASTEWATER PERM INSPECTION | ¤80.00 | 12/23/2025 |
| WASTEWATER PERM REVIEW | ¤25.00 | 12/23/2025 |
| SEWER CAPITAL FACILITY | ¤3,628.86 | 12/23/2025 |
| WATER CAPITAL FACILITY FEE | ¤3,091.14 | 12/23/2025 |
| WATER PERMIT REVIEW | ¤25.00 | 12/23/2025 |
| SITE PLAN 30 | ¤30.00 | 12/23/2025 |
| WATER-METER | ¤874.47 | 12/23/2025 |
| WATER- TURN ON | ¤50.00 | 12/23/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 12/23/2025 |
| INSPECTION - RESIDENTIAL | ¤899.25 | 12/23/2025 |
| PLAN REVIEW - RESIDENTIAL | ¤255.06 | 12/23/2025 |
| REINSPECTION RESIDENTIAL | ¤40.00 | |
| Fees | Total Due: ¤40.00 | Total Paid: ¤26,530.18 |