I want to search for...
Permit #2025110353
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7034-01590-0180 |
| Block: 01590 |
| Subdivision: 7034 - |
| Job Phone: 386-586-6290 |
| Location Address: 201 ERIC DR |
| Type: ME - MECHANICAL |
| Issue Date: 11/12/2025 |
| NOC: Unknown |
| Applicant name: RICHARD GARY WILSON JR |
| Owner: BLONDER SALLY L & FREDERICA LEWIS TRUSTEES |
|
Address 201 ERIC DR PALM COAST, FL 32164 |
| Lot: 0180 |
| Contracted Stated Job Value: ¤8,655.00 |
| Job Description: HVAC Change-out 4 Ton like for like |
| Type: CN |
Contractor
R.W. AIRE CONDITIONING AND HEATING INC
| Status | Location Address | Mailing Address | State License Number | Phone |
| ACTIVE |
1504 OLD MOODY BLVD BUNNELL, FL 32110 |
UNIT 6 BUNNELL, FL 32110 |
CAC1817645 (Exp: 08/31/2026) | 386-586-6290 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 12/02/2025 | FINAL APPROVED | CVANSTRAHLEN |
| Note: 11/20/2025 - PREVIOUS INSPECTION NOTES 11/20/25: 1). Breaker for Outside condensing unit is too big. (Min.-25.5 amp / Max.-40 amp / 50 amp installed). | |||
| HVAC FINAL | 11/20/2025 | Disapproved -FEE REQUIRED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 11/20/2025 3:01:11 PM *** 11/20/25: 1). Breaker for Outside condensing unit is too big. (Min.-25.5 amp / Max.-40 amp / 50 amp installed). |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 12/01/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 11/12/2025 |
| SURCHARGE - FS 468.631 | ¤2.00 | 11/12/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 11/12/2025 |
| INSPECTION - MECHANICAL | ¤60.00 | 11/12/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤134.00 |