I want to search for...
Permit #2025120425
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7057-00110-0010 |
| Block: 00110 |
| Subdivision: 2123 - SECTION 57-ULYSSES TREES |
| Job Phone: 386-439-3416 |
| Location Address: 26 UTIDE CT |
| Type: ME - MECHANICAL |
| Issue Date: 12/11/2025 |
| NOC: Unknown |
| Applicant name: CHARLES WEYANT |
| Owner: VINING DOUGLAS & BONNIE H&W |
|
Address 26 UTIDE COURT PALM COAST, FL 32164 |
| Lot: 0010 |
| Contracted Stated Job Value: ¤12,191.00 |
| Job Description: HVAC equipment change-out - Like for Like 3 Ton |
| Type: CN |
Contractor
ACCU TEMP HEATING & AIR CONDITIONING INC.
| Status | Location Address | State License Number | Phone |
| ACTIVE |
PO BOX 1261 FLAGLER BEACH, FL 32136 |
CAC1815058 (Exp: 08/31/2026) | (386)246-7745 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 04/10/2026 | APPROVED | CVANSTRAHLEN |
| Note: 3/18/2026 - PREVIOUS INSPECTION NOTES 3/18/26 1. Wrong size breaker for ODU. Max 25amp and 35amp is installed NEC 440.4 2. Heat strips not marked on AH so could not verify amperage required FBCR M1303.1 | |||
| HVAC FINAL | 03/18/2026 | Disapproved - NO FEE | MCONTRYMAN |
| Note: 3/18/26 1. Wrong size breaker for ODU. Max 25amp and 35amp is installed NEC 440.4 2. Heat strips not marked on AH so could not verify amperage required FBCR M1303.1 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 12/11/2025 |
| INSPECTION - MECHANICAL | ¤60.00 | 12/11/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 12/11/2025 |
| SURCHARGE - FS 468.631 | ¤2.00 | 12/11/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤94.00 |