I want to search for...

Permit #2026010034

Permit Details

Status: FINAL

Parcel Id: 42-10-30-3210-00000-1840
Block: 00000
Subdivision: 2094 - CONSERVATORY AT HAMMOCK BEACH
Job Phone: 352-629-8617
Location Address: 425 BOURGANVILLE DR
Type: GEN - GENERATOR
Issue Date: 01/08/2026
NOC: RECORDED
Applicant name: CHISTOPHER J SHEA
Owner: FAKE, RONALD & JOANNE

Address

425 BOURGANVILLE DR

PALM COAST, FL 32137

Lot: 184
Contracted Stated Job Value: ¤14,200.00
Job Description: 22KW GENERATOR WITH A 200AMP TRANSFER SWITCH.
Type: CN

Contractor

TRADEMARK ELECTRIC, INC
Status Location Address State License Number Phone Fax
ACTIVE

3621 NW 27TH AVE

OCALA, FL 34475

EC13004066 (Exp: 08/31/2026) 352-629-8617 352-629-2551

Inspection History

Type Request Date Result Inspector
ELECTRIC FINAL 02/26/2026 FINAL APPROVED RMARTIN
Note: 2/10/2026 - PREVIOUS INSPECTION NOTES 1. Gas final has not been approved, must call in gas final before generator final and start up can be done 2. Generator contractor must be onsite to open ATS and do a start up per COPC Building Dept. 3. Full set of plans needs to be onsite with Building Dept. stamp of approval FBC 107.3.1
GAS ROUGH 02/10/2026 CANCELLED BY INSPECTOR MKRASKI
Note: Not needed, gas permit by others
GAS FINAL 02/10/2026 CANCELLED BY INSPECTOR MKRASKI
Note: Not needed, gas permit by others
ELECTRIC FINAL 02/10/2026 Disapproved - NO FEE MKRASKI
Note: 1. Gas final has not been approved, must call in gas final before generator final and start up can be done 2. Generator contractor must be onsite to open ATS and do a start up per COPC Building Dept. 3. Full set of plans needs to be onsite with Building Dept. stamp of approval FBC 107.3.1

Review History

Department Status Date In Date Out
GAS COMPLETE 01/07/2026 01/08/2026
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ELEC COMPLETE 01/06/2026 01/07/2026
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
GAS HOLD 01/06/2026 01/07/2026
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final.
ZON COMPLETE 01/06/2026 01/06/2026
Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADMINISTRATIVE RESIDENTIAL ¤30.00 01/08/2026
INSPECTION - RESIDENTIAL ¤60.00 01/08/2026
PLAN REVIEW - MISC 32.50 ¤32.50 01/08/2026
SURCHARGE FS 533.721 ¤2.00 01/08/2026
SURCHARGE - FS 468.631 ¤2.00 01/08/2026
SITE PLAN 15 ¤15.00 01/08/2026
Fees Total Due: ¤0.00 Total Paid: ¤141.50