I want to search for...
Permit #2026010034
Permit Details
Status: FINAL
| Parcel Id: 42-10-30-3210-00000-1840 |
| Block: 00000 |
| Subdivision: 2094 - CONSERVATORY AT HAMMOCK BEACH |
| Job Phone: 352-629-8617 |
| Location Address: 425 BOURGANVILLE DR |
| Type: GEN - GENERATOR |
| Issue Date: 01/08/2026 |
| NOC: RECORDED |
| Applicant name: CHISTOPHER J SHEA |
| Owner: FAKE, RONALD & JOANNE |
|
Address 425 BOURGANVILLE DR PALM COAST, FL 32137 |
| Lot: 184 |
| Contracted Stated Job Value: ¤14,200.00 |
| Job Description: 22KW GENERATOR WITH A 200AMP TRANSFER SWITCH. |
| Type: CN |
Contractor
TRADEMARK ELECTRIC, INC
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
3621 NW 27TH AVE OCALA, FL 34475 |
EC13004066 (Exp: 08/31/2026) | 352-629-8617 | 352-629-2551 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 02/26/2026 | FINAL APPROVED | RMARTIN |
| Note: 2/10/2026 - PREVIOUS INSPECTION NOTES 1. Gas final has not been approved, must call in gas final before generator final and start up can be done 2. Generator contractor must be onsite to open ATS and do a start up per COPC Building Dept. 3. Full set of plans needs to be onsite with Building Dept. stamp of approval FBC 107.3.1 | |||
| GAS ROUGH | 02/10/2026 | CANCELLED BY INSPECTOR | MKRASKI |
| Note: Not needed, gas permit by others | |||
| GAS FINAL | 02/10/2026 | CANCELLED BY INSPECTOR | MKRASKI |
| Note: Not needed, gas permit by others | |||
| ELECTRIC FINAL | 02/10/2026 | Disapproved - NO FEE | MKRASKI |
| Note: 1. Gas final has not been approved, must call in gas final before generator final and start up can be done 2. Generator contractor must be onsite to open ATS and do a start up per COPC Building Dept. 3. Full set of plans needs to be onsite with Building Dept. stamp of approval FBC 107.3.1 |
Review History
| Department | Status | Date In | Date Out |
| GAS | COMPLETE | 01/07/2026 | 01/08/2026 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 01/06/2026 | 01/07/2026 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| GAS | HOLD | 01/06/2026 | 01/07/2026 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. | |||
| ZON | COMPLETE | 01/06/2026 | 01/06/2026 |
| Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 01/08/2026 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 01/08/2026 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 01/08/2026 |
| SURCHARGE FS 533.721 | ¤2.00 | 01/08/2026 |
| SURCHARGE - FS 468.631 | ¤2.00 | 01/08/2026 |
| SITE PLAN 15 | ¤15.00 | 01/08/2026 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤141.50 |