I want to search for...
Permit #2026010360
Permit Details
Status: ISSUED
| Parcel Id: 07-11-31-7010-00070-0700 |
| Total Square Footage: 2 sqft |
| Block: 00070 |
| Subdivision: - |
| Job Phone: 407-963-7173 |
| Location Address: 27 FLEMINGWOOD LN |
| Type: ME - MECHANICAL |
| Issue Date: 01/29/2026 |
| NOC: Unknown |
| Applicant name: CHRISTOPHER ALAN HANMER |
| Owner: LAMBERT MARIA THERESE |
|
Address 27B FLEMINGWOO LANE PALM COAST, FL 32137 |
| Lot: 0700 |
| Contracted Stated Job Value: ¤9,325.00 |
| Job Description: HVAC LIKE FOR LIKE TONNAGE - REF: 2025061073 |
| Type: CN |
| Original Permit #: 2025061073 |
Contractor
FLORIDA ENERGY WATER & AIR
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
6505 EDGEWATER DRIVE ORLANDO, FL 32810 |
CAC057033 (Exp: 08/31/2026) | 800-382-7638 | 407-523-8668 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 09/29/2025 | Disapproved -FEE REQUIRED | JSTEWART |
| Note: 1. Please install/lock (3) service caps at AC conditioner. FBCR M1411.8 2. Please seal garage ceiling at Plenum Penetration. FBC EC TABLE R402.4.1.1 3. No AHRI cert onsite. FBC EC R303.1.2 / C403.2.3 | |||
| HVAC FINAL | |||
| Note: 9/29/2025 - PREVIOUS INSPECTION NOTES 1. Please install/lock (3) service caps at AC conditioner. FBCR M1411.8 2. Please seal garage ceiling at Plenum Penetration. FBC EC TABLE R402.4.1.1 3. No AHRI cert onsite. FBC EC R303.1.2 / C403.2.3 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 01/29/2026 |
| INSPECTION - MECHANICAL | ¤60.00 | 01/29/2026 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 01/29/2026 |
| SURCHARGE FS 533.721 | ¤2.00 | 01/29/2026 |
| SURCHARGE - FS 468.631 | ¤2.00 | 01/29/2026 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤134.00 |