Permit #2026010451

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7026-00720-0310
Block: 00720
Subdivision: -
Job Phone: 386-439-3333
Location Address: 28 PITTWICK LN
Type: PL - PLUMBING
Issue Date: 01/16/2026
NOC: RECORDED
Applicant name: JAMES WILLIAM SINCLAIR
Owner: MILLER MARGARET G & MILLER HARRY P JTWROS

Address

28 PITTWICK LN

PALM COAST, FL 32164

Lot: 0310
Contracted Stated Job Value: ¤17,443.96
Job Description: Whole House repipe
Type: CN

Contractor

MR. ROOTER PLUMBING
Status Location Address State License Number Phone
ACTIVE

501 SOUTH 27TH STREET

BUNNELL, FL 32110

CFC1429533 (Exp: 08/31/2026) 386-439-3333

Inspection History

Type Request Date Result Inspector
PLUMBING FINAL 04/06/2026 FINAL APPROVED PKNAPIK
Note: 3/31/2026 - PREVIOUS INSPECTION NOTES 1. Dishwasher needs hammer arrester. FBCR P2903.5 2. Need to seal holes in the garage ceiling where the pipes go through. R302.5 3. Homeowner states that the re-circ. pump is not working/set properly.
PLUMBING FINAL 03/31/2026 Disapproved - NO FEE HCAMACHO
Note: 1. Dishwasher needs hammer arrester. FBCR P2903.5 2. Need to seal holes in the garage ceiling where the pipes go through. R302.5 3. Homeowner states that the re-circ. pump is not working/set properly.
PLUMBING 2ND ROUGH 02/04/2026 APPROVED RSIMS
Note: *** NOTES ADDED BY RSIMS 2/4/2026 11:06:54 AM *** 1/23/2026 - PREVIOUS INSPECTION NOTES 1/23/25: 1). Cold water line under kitchen sink needs to be secured with clamps per FBC-P2605.1. (per FPC - table 308.5) 2). Water lines feeding guest bathroom need to be secured in the wall. FBC-P2605.1. (per FPC - table 308.5) 3). Water lines in the attic need to be secured as required. FBC-P2605.1. (per FPC - table 308.5)
PLUMBING 2ND ROUGH 01/23/2026 Disapproved -FEE REQUIRED RSIMS
Note: *** NOTES ADDED BY RSIMS 1/23/2026 12:10:02 PM *** Please check all locations. 1/23/25: 1). Cold water line under kitchen sink needs to be secured with clamps per FBC-P2605.1. (per FPC - table 308.5) 2). Water lines feeding guest bathroom need to be secured in the wall. FBC-P2605.1. (per FPC - table 308.5) 3). Water lines in the attic need to be secured as required. FBC-P2605.1. (per FPC - table 308.5)

Review History

Department Status Date In Date Out
PLUM COMPLETE 01/15/2026 01/16/2026
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 01/29/2026
SURCHARGE FS 533.721 ¤2.00 01/16/2026
SURCHARGE - FS 468.631 ¤2.00 01/16/2026
ADMINISTRATIVE RESIDENTIAL ¤30.00 01/16/2026
INSPECTION - PLUMBING ¤60.00 01/16/2026
PLAN REVIEW - MISC 32.50 ¤32.50 01/16/2026
Fees Total Due: ¤0.00 Total Paid: ¤166.50