Permit #2026010699

Permit Details

Status: COED

Parcel Id: 04-11-30-5571-00000-3340
CONDITIONED SPACE: 1638 sqft
GARAGE: 461 sqft
OPENED PORCH (WITH ROOF) : 96 sqft
OPENED PORCH (WITH ROOF) : 112 sqft
Total Square Footage: 2307 sqft
Subdivision: 2366 - SOMERSET SUBDIVISION PH 2
Job Phone: 904-596-6645
Location Address: 37 SOMERSET AVE
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 02/06/2026
NOC: RECORDED
Applicant name: MICHAEL T HOLDER
Owner: KB HOME JACKSONVILLE LLC

Address

10475 FORTUNE PARKWAY

JACKSONVILLE, FL 32256

Address

SUITE 100

JACKSONVILLE, FL 32256

Lot: 334
Contracted Stated Job Value: ¤140,000.00
Job Description: SINGLE FAMILY DWELLING
Type: CN

Contractor

KB HOME JACKSONVILLE, LLC
Status Location Address Mailing Address State License Number Phone
ACTIVE

10475 FORTUNE PKWY

JACKSONVILLE, FL 32256

SUITE 100

JACKSONVILLE, FL 32256

CGC1509034 (Exp: 08/31/2026) 904-596-6645

Sub Contractors

LARRY WILLIAMS
Status Location Address State License Number Phone
ACTIVE

1750 EMERSON ST

JACKSONVILLE, FL 32207

LI45034 (Exp: 08/31/2026) 904-721-5431
BOBBY WAYNE CAMPBELL
Status Location Address State License Number Phone
ACTIVE

117 GUTHRIE ROAD

GREEN COVE SPRINGS, FL 32043

CCC1326752 (Exp: 08/31/2026) 904-200-1600
JAMES E LINTON
Status Location Address State License Number Phone
ACTIVE

200 COLLEGE DR

ORANGE PARK, FL 32065

EC0001152 (Exp: 08/31/2026) 904-272-0272
COREY MICHAEL TENNANT
Status Location Address State License Number Phone
ACTIVE

3370 AGRICULTURAL CNETER DR

ST AUGUSTINE, FL 32092

CAC1819063 (Exp: 08/31/2026) 904-829-8898
BENJAMIN MICHAEL RAY
Status Location Address Mailing Address State License Number Phone Fax
ACTIVE

6310 MABLETON PKWY

JACKSONVILLE, FL 32216

SUITE 1000

MABLETON, GA 30126

CFC1428415 (Exp: 08/31/2026) 904-861-5421 904-861-5426

Inspection History

Type Request Date Result Inspector
ROW - FINAL INSPECTION 05/28/2026 APPROVED TPOLACEK
Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. NIETHER THE INSPECTOR NOR THE CITY IS RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED 5/27/2026 - PREVIOUS INSPECTION NOTES ** 05/27/26 BUILDER IS REQUIRED TO PUT EROSION AND SEDIMENTCONTROL DEVICE BACKIN PLACE ALONG THE CURB AND GUTTER ON EITHER SIDE OF 37 SOMERSET. ** SOD REMAINING BARE EARTH AROUND ELECTRIC UTILITY BOX ON LEFT SIDE PROPERTY TO AID IN EROSION CONTROL ** REPAIR SILT FENCE ALONG REAR OF BOTH 35 AND 39 VACANT LOTS ____________________________________________________________________________________________________________________________ Inspector Notes from Inspection 9270 ** 0421/26 CORRECTIONS MADE ** READY TO POUR ** AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. NIETHER THE INSPECTOR NOR THE CITY IS RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED **MAKE SURE THERE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE __________________________________________________________________________________________________________________________ 4/20/2026 - PREVIOUS INSPECTION NOTES ** 04/20/26 INSPECTOR HIT THE SAVE BUTTON INADVERTANTLY BEFORE ALL NOTES WERE COMPLETED FOR THIS PRE-POUR INSPECTION WHICH IS WHY THE SECOND DISAPPROVED INSPECTION WAS COMPLETED YOU WERE ONLY FEED ONCE FOR THIS INSPECTION ** A MINIMUM OF 4 INCHES OF CONCRETE IS REQUIRED IN THE POUR AREA ABOVE THE APRON AREA NEED TO LOWER POWER AREA TO ACHIEVE THE 4 INCHES. (NOTE STRINGLINES LEFT IN PLACE ** THE ELEPHANTS FOOT FOR SEWER IS TIPPED FORWARD AND WILL NOT BE FLUSH WITH CONCRETE AS REQUIRED ** WATER SHUT-OFF IN SIDEWALK ON RIGHT SIDE IS BELOW THE TOP OF FORM BOARDS NEEDS TO BE FLUSH TO SURFACE TOP OF FORMS SO A TRIPPING HAZZARD IS NOT CREATED ** SEE ATTACHED PHOTOS _____________________________________________________________________________________________________________________________ 4/20/2026 - PREVIOUS INSPECTION NOTES ** 04/20/26 A MINIMUM OF 4 INCHES OF CONCRETE IS REQUIRED IN THE POUR AREA ABOVE THE APRON AREA NEED TO LOWER POWER AREA TO ACHIEVE THE 4 INCHES. ** THE ELEPHANTS FOOT FOR SEWER IS TIPPED FORWARD AND WILL NOT BE FLUSH WITH CONCRETE AS REQUIRED
U -UTILITY RESIDENTIAL FINAL 05/28/2026 FINAL APPROVED BHAINES
Note: 5/27/2026 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9035 NO CC / IRR with reclaim. Fire Hydrant needs brass tag for valve.
U -UTILITY RESIDENTIAL FINAL 05/27/2026 Disapproved - NO FEE BWRIGHT
Note: Inspector Notes from Inspection 9035 NO CC / IRR with reclaim. Fire Hydrant needs brass tag for valve.
ROW - FINAL APRON (AFTER POUR) 05/27/2026 APPROVED EMADISON
Note: ** AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. NIETHER THE INSPECTOR NOR THE CITY IS RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED
ROW - FINAL INSPECTION 05/27/2026 Disapproved -FEE REQUIRED EMADISON
Note: ** 05/27/26 BUILDER IS REQUIRED TO PUT EROSION AND SEDIMENTCONTROL DEVICE BACKIN PLACE ALONG THE CURB AND GUTTER ON EITHER SIDE OF 37 SOMERSET. ** SOD REMAINING BARE EARTH AROUND ELECTRIC UTILITY BOX ON LEFT SIDE PROPERTY TO AID IN EROSION CONTROL ** REPAIR SILT FENCE ALONG REAR OF BOTH 35 AND 39 VACANT LOTS ____________________________________________________________________________________________________________________________ Inspector Notes from Inspection 9270 ** 0421/26 CORRECTIONS MADE ** READY TO POUR ** AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. NIETHER THE INSPECTOR NOR THE CITY IS RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED **MAKE SURE THERE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE __________________________________________________________________________________________________________________________ 4/20/2026 - PREVIOUS INSPECTION NOTES ** 04/20/26 INSPECTOR HIT THE SAVE BUTTON INADVERTANTLY BEFORE ALL NOTES WERE COMPLETED FOR THIS PRE-POUR INSPECTION WHICH IS WHY THE SECOND DISAPPROVED INSPECTION WAS COMPLETED YOU WERE ONLY FEED ONCE FOR THIS INSPECTION ** A MINIMUM OF 4 INCHES OF CONCRETE IS REQUIRED IN THE POUR AREA ABOVE THE APRON AREA NEED TO LOWER POWER AREA TO ACHIEVE THE 4 INCHES. (NOTE STRINGLINES LEFT IN PLACE ** THE ELEPHANTS FOOT FOR SEWER IS TIPPED FORWARD AND WILL NOT BE FLUSH WITH CONCRETE AS REQUIRED ** WATER SHUT-OFF IN SIDEWALK ON RIGHT SIDE IS BELOW THE TOP OF FORM BOARDS NEEDS TO BE FLUSH TO SURFACE TOP OF FORMS SO A TRIPPING HAZZARD IS NOT CREATED ** SEE ATTACHED PHOTOS _____________________________________________________________________________________________________________________________ 4/20/2026 - PREVIOUS INSPECTION NOTES ** 04/20/26 A MINIMUM OF 4 INCHES OF CONCRETE IS REQUIRED IN THE POUR AREA ABOVE THE APRON AREA NEED TO LOWER POWER AREA TO ACHIEVE THE 4 INCHES. ** THE ELEPHANTS FOOT FOR SEWER IS TIPPED FORWARD AND WILL NOT BE FLUSH WITH CONCRETE AS REQUIRED
BLD - BUILDING FINAL 05/27/2026 FINAL APPROVED JSTEWART
Note: 5/26/2026 - PREVIOUS INSPECTION NOTES Via text 5/22/2026 - PREVIOUS INSPECTION NOTES 1. Anti tip on Oven is not installed.FBCR M1901.2 2. Master shower valve not installed. FBCR P2705.1
BLD - BUILDING FINAL 05/26/2026 CANCELLED BY APPLICANT HCAMACHO
Note: Via text 5/22/2026 - PREVIOUS INSPECTION NOTES 1. Anti tip on Oven is not installed.FBCR M1901.2 2. Master shower valve not installed. FBCR P2705.1
U-CROSS CONNECTION 05/22/2026 APPROVED - AS NOTED TLOWE
Note: NO CC / IRR with reclaim.
BLD - BUILDING FINAL 05/22/2026 Disapproved - NO FEE HCAMACHO
Note: 1. Anti tip on Oven is not installed.FBCR M1901.2 2. Master shower valve not installed. FBCR P2705.1
ELECTRIC - EARLY POWER 05/04/2026 APPROVED JSTEWART
Note: Inspector Notes from Inspection 2200 Authorize release of email.
ROW- PRE-APRON (PRE-POUR) 04/21/2026 APPROVED - AS NOTED EMADISON
Note: ** 0421/26 CORRECTIONS MADE ** READY TO POUR ** AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. NIETHER THE INSPECTOR NOR THE CITY IS RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED **MAKE SURE THERE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE __________________________________________________________________________________________________________________________ 4/20/2026 - PREVIOUS INSPECTION NOTES ** 04/20/26 INSPECTOR HIT THE SAVE BUTTON INADVERTANTLY BEFORE ALL NOTES WERE COMPLETED FOR THIS PRE-POUR INSPECTION WHICH IS WHY THE SECOND DISAPPROVED INSPECTION WAS COMPLETED YOU WERE ONLY FEED ONCE FOR THIS INSPECTION ** A MINIMUM OF 4 INCHES OF CONCRETE IS REQUIRED IN THE POUR AREA ABOVE THE APRON AREA NEED TO LOWER POWER AREA TO ACHIEVE THE 4 INCHES. (NOTE STRINGLINES LEFT IN PLACE ** THE ELEPHANTS FOOT FOR SEWER IS TIPPED FORWARD AND WILL NOT BE FLUSH WITH CONCRETE AS REQUIRED ** WATER SHUT-OFF IN SIDEWALK ON RIGHT SIDE IS BELOW THE TOP OF FORM BOARDS NEEDS TO BE FLUSH TO SURFACE TOP OF FORMS SO A TRIPPING HAZZARD IS NOT CREATED ** SEE ATTACHED PHOTOS _____________________________________________________________________________________________________________________________ 4/20/2026 - PREVIOUS INSPECTION NOTES ** 04/20/26 A MINIMUM OF 4 INCHES OF CONCRETE IS REQUIRED IN THE POUR AREA ABOVE THE APRON AREA NEED TO LOWER POWER AREA TO ACHIEVE THE 4 INCHES. ** THE ELEPHANTS FOOT FOR SEWER IS TIPPED FORWARD AND WILL NOT BE FLUSH WITH CONCRETE AS REQUIRED
ROW- PRE-APRON (PRE-POUR) 04/20/2026 Disapproved -FEE REQUIRED EMADISON
Note: ** 04/20/26 A MINIMUM OF 4 INCHES OF CONCRETE IS REQUIRED IN THE POUR AREA ABOVE THE APRON AREA NEED TO LOWER POWER AREA TO ACHIEVE THE 4 INCHES. ** THE ELEPHANTS FOOT FOR SEWER IS TIPPED FORWARD AND WILL NOT BE FLUSH WITH CONCRETE AS REQUIRED
ROW- PRE-APRON (PRE-POUR) 04/20/2026 Disapproved - NO FEE EMADISON
Note: ** 04/20/26 INSPECTOR HIT THE SAVE BUTTON INADVERTANTLY BEFORE ALL NOTES WERE COMPLETED FOR THIS PRE-POUR INSPECTION WHICH IS WHY THE SECOND DISAPPROVED INSPECTION WAS COMPLETED YOU WERE ONLY FEED ONCE FOR THIS INSPECTION ** A MINIMUM OF 4 INCHES OF CONCRETE IS REQUIRED IN THE POUR AREA ABOVE THE APRON AREA NEED TO LOWER POWER AREA TO ACHIEVE THE 4 INCHES. (NOTE STRINGLINES LEFT IN PLACE ** THE ELEPHANTS FOOT FOR SEWER IS TIPPED FORWARD AND WILL NOT BE FLUSH WITH CONCRETE AS REQUIRED ** WATER SHUT-OFF IN SIDEWALK ON RIGHT SIDE IS BELOW THE TOP OF FORM BOARDS NEEDS TO BE FLUSH TO SURFACE TOP OF FORMS SO A TRIPPING HAZZARD IS NOT CREATED ** SEE ATTACHED PHOTOS _____________________________________________________________________________________________________________________________ 4/20/2026 - PREVIOUS INSPECTION NOTES ** 04/20/26 A MINIMUM OF 4 INCHES OF CONCRETE IS REQUIRED IN THE POUR AREA ABOVE THE APRON AREA NEED TO LOWER POWER AREA TO ACHIEVE THE 4 INCHES. ** THE ELEPHANTS FOOT FOR SEWER IS TIPPED FORWARD AND WILL NOT BE FLUSH WITH CONCRETE AS REQUIRED
DRYWALL NAILING 04/13/2026 APPROVED JSTEWART
INSULATION 04/09/2026 APPROVED JSTEWART
Note: 4/8/2026 - PREVIOUS INSPECTION NOTES Previous Note (Twice) not rectified......Spare bath exhaust duct required to be sealed and mechanically fastened to the fan assembly. FBCR M1601.4.1 / M1501.1 1. Electricians are onsite pulling and running romex top plate penetrations will need firestoped when work is complete. FBC R302.11(4) Inspector Notes from Inspection 2420 Check #5 4/2/2026 - PREVIOUS INSPECTION NOTES 1. Gas pipe runs not complete, needs to penetrate the exterior walls, No runs to Kitchen, Laundry and porch. per plan 2. Gas Bonding.FBCR G2411 3. Gas preassure test. FBCR G2417.4.1 4. Multiple location romex sheathing required to enter holding box Min 1/4". NEC 314.17(C) 5. Spare bath exhaust duct required to be sealed and mechanically fastened to the fan assembly. FBCR M1601.4.1 Will need to be repaired prior to insulation, so items are open for inspection.
INSULATION 04/08/2026 Disapproved -FEE REQUIRED JSTEWART
Note: Previous Note (Twice) not rectified......Spare bath exhaust duct required to be sealed and mechanically fastened to the fan assembly. FBCR M1601.4.1 / M1501.1 1. Electricians are onsite pulling and running romex top plate penetrations will need firestoped when work is complete. FBC R302.11(4) Inspector Notes from Inspection 2420 Check #5 4/2/2026 - PREVIOUS INSPECTION NOTES 1. Gas pipe runs not complete, needs to penetrate the exterior walls, No runs to Kitchen, Laundry and porch. per plan 2. Gas Bonding.FBCR G2411 3. Gas preassure test. FBCR G2417.4.1 4. Multiple location romex sheathing required to enter holding box Min 1/4". NEC 314.17(C) 5. Spare bath exhaust duct required to be sealed and mechanically fastened to the fan assembly. FBCR M1601.4.1 Will need to be repaired prior to insulation, so items are open for inspection.
ELECTRIC-TUG 04/08/2026 APPROVED - AS NOTED JSTEWART
Note: Authorize release of email.
LATH/BRICK/ WATER BARRIER 04/06/2026 APPROVED KSANDOE
Note: 4/2/2026 - PREVIOUS INSPECTION NOTES 1. Missing water barrier at (2) porch post at base. 2. Gas piping needs to Penetrate exterior wall at connection and back porch, and water barrier installed.
ALL ROUGH 04/06/2026 APPROVED - AS NOTED KSANDOE
Note: Check #5 4/2/2026 - PREVIOUS INSPECTION NOTES 1. Gas pipe runs not complete, needs to penetrate the exterior walls, No runs to Kitchen, Laundry and porch. per plan 2. Gas Bonding.FBCR G2411 3. Gas preassure test. FBCR G2417.4.1 4. Multiple location romex sheathing required to enter holding box Min 1/4". NEC 314.17(C) 5. Spare bath exhaust duct required to be sealed and mechanically fastened to the fan assembly. FBCR M1601.4.1 Will need to be repaired prior to insulation, so items are open for inspection.
ALL ROUGH 04/02/2026 Disapproved - NO FEE JSTEWART
Note: 1. Gas pipe runs not complete, needs to penetrate the exterior walls, No runs to Kitchen, Laundry and porch. per plan 2. Gas Bonding.FBCR G2411 3. Gas preassure test. FBCR G2417.4.1 4. Multiple location romex sheathing required to enter holding box Min 1/4". NEC 314.17(C) 5. Spare bath exhaust duct required to be sealed and mechanically fastened to the fan assembly. FBCR M1601.4.1 Will need to be repaired prior to insulation, so items are open for inspection.
LATH/BRICK/ WATER BARRIER 04/02/2026 Disapproved - NO FEE JSTEWART
Note: 1. Missing water barrier at (2) porch post at base. 2. Gas piping needs to Penetrate exterior wall at connection and back porch, and water barrier installed.
GRAVITY SEWER TEST 03/30/2026 APPROVED JSTEWART
Note: Live virtual Inspection. Note: Main water line from utility tap to Building installed, Inspector Notes from Inspection 2060 Main water line from utility tap to Building not installed, This will be required to be installed and open for inspection at the All Rough inspection. Under the FBC [A]110.3 Required inspections. (Plumbing) (1.). This part of the Plumbing (underground) falls in the criteria of 1st rough plumbing inspection.
SEWER TIE IN 03/30/2026 APPROVED JSTEWART
Note: Live virtual Inspection. Note: Main water line from utility tap to Building installed, Inspector Notes from Inspection 2060 Main water line from utility tap to Building not installed, This will be required to be installed and open for inspection at the All Rough inspection. Under the FBC [A]110.3 Required inspections. (Plumbing) (1.). This part of the Plumbing (underground) falls in the criteria of 1st rough plumbing inspection.
WALL SHEATHING 03/30/2026 APPROVED JSTEWART
Note: Inspector Notes from Inspection 2467
ROOF SHEATHING / BRACES/TIES/DOWN CELL 03/27/2026 APPROVED - AS NOTED JSTEWART
Note: Unable to see porch post dry bottom fasteners. please uncover will Check at wall sheathing re inspection. FBC [A]110.1
ROOF VALLEY & METAL 03/27/2026 APPROVED - AS NOTED JSTEWART
WALL SHEATHING 03/27/2026 Disapproved - NO FEE JSTEWART
Note: All seams and perimeter has been covererd with tape. Please remove tape for Inspection. [A]110.1 General....shall be subject to inspection by the building official and such construction or work shall remain exposed and provided with access for inspection purposes until approved.
MONOLITHIC SLAB 03/12/2026 APPROVED JSTEWART
Note: 3/11/2026 - PREVIOUS INSPECTION NOTES 1. Rebar at garage curb step up needs positioned for clearence from form board min of 1 1/2". 2. Vapor barrier needs to be cut out for the required 20ft of the Ufer ground (concrete encased electrode), requires direct contact with earth. NEC 250.52(A)(3)
MONOLITHIC SLAB 03/11/2026 Disapproved - NO FEE JSTEWART
Note: 1. Rebar at garage curb step up needs positioned for clearence from form board min of 1 1/2". 2. Vapor barrier needs to be cut out for the required 20ft of the Ufer ground (concrete encased electrode), requires direct contact with earth. NEC 250.52(A)(3)
PLUMBING 1ST ROUGH UNDERGROUND 03/10/2026 APPROVED - AS NOTED JSTEWART
Note: Main water line from utility tap to Building not installed, This will be required to be installed and open for inspection at the All Rough inspection. Under the FBC [A]110.3 Required inspections. (Plumbing) (1.). This part of the Plumbing (underground) falls in the criteria of 1st rough plumbing inspection.
FORMBOARD SURVEY (OFFICE USE ONLY) 03/09/2026 APPROVED RRICKS
WATER METER INSTALLATION REQUEST 03/03/2026 APPROVED ISANDERSON

Review History

Department Status Date In Date Out
SW1 HOLD 03/09/2026 03/09/2026
Note: Held By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM
SW1 COMPLETE 03/09/2026 03/09/2026
Note: Released By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM
SW1 HOLD 03/02/2026 03/03/2026
Note: Held By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM There is no approved grading plan on file. Please submit grading plan
ZON COMPLETE 03/02/2026 03/02/2026
Note: Released By: MICHELLE RAMOS - (386)986-3780 - MRAMOS@PALMCOASTGOV.COM
ZON COMPLETE 02/04/2026 02/04/2026
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
SW1 COMPLETE 01/28/2026 01/28/2026
Note: Released By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM
BLD COMPLETE 01/22/2026 01/27/2026
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
CUSVC COMPLETE 01/22/2026 01/30/2026
Note: Released By: HALEIGH HAND - - HHAND@PALMCOASTGOV.COM Utility fees paid on previous permit and meter is already installed. No additional fees owed.
ELEC COMPLETE 01/22/2026 01/27/2026
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ENGIN1 COMPLETE 01/22/2026 01/23/2026
Note: Released By: LEVI SALYERDS - (386)986-2575 - LSALYERDS@PALMCOASTGOV.COM
GAS COMPLETE 01/22/2026 01/23/2026
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
LOCATE COMPLETE 01/22/2026 01/30/2026
Note: Released By: CANDACE BOWERMASTER - - CBOWERMASTER@PALMCOASTGOV.COM
MECH COMPLETE 01/22/2026 01/26/2026
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ZON HOLD 01/22/2026 01/26/2026
Note: Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM There is already another permit on this property and now you have requested another permit at the same address. Please get with zoning 386-986-4737
URB COMPLETE 01/22/2026 01/29/2026
Note: Released By: JOHN BEAUDET - (386)986-2456 - JBEAUDET@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
RSI REINSPECTION 1 ¤35.00 05/27/2026
REINSPECTION RESIDENTIAL ¤40.00 05/26/2026
RSI REINSPECTION 1 ¤35.00 05/26/2026
ADMINISTRATIVE RESIDENTIAL ¤30.00 02/06/2026
INSPECTION - RESIDENTIAL ¤899.25 02/06/2026
PLAN REVIEW - RESIDENTIAL ¤255.06 02/06/2026
FC IMPACT FEE EMS ¤62.00 02/06/2026
FC IMPACT FEE LAW ENFORCEMENT ¤218.00 02/06/2026
FC IMPACT FEE LIBRARY ¤268.00 02/06/2026
FIRE RES IMPACT FEE 10-25 ¤942.00 02/06/2026
PARKS IMPACT FEE 10-25 ¤3,164.00 02/06/2026
RSI DRIVEWAY AFTER POUR ¤16.25 02/06/2026
RSE DRIVE PRE POUR INSPECTION ¤32.50 02/06/2026
RSI FIELD SURVEY INSPECTION ¤48.75 02/06/2026
RSI FORMBOARD REVIEW ¤16.25 02/06/2026
RSI PLAN REVIEW NEW ¤48.75 02/06/2026
RSI FNL SURVEY/GRADING CERT ¤48.75 02/06/2026
RSI ROW FINAL INSPECTION ¤16.25 02/06/2026
SCHOOL BOARD IMPACT FEE RES ¤5,450.00 02/06/2026
SURCHARGE FS 533.721 ¤11.84 02/06/2026
SURCHARGE - FS 468.631 ¤17.77 02/06/2026
TRANSP RES IMPACT FEE 10-25 ¤6,175.26 02/06/2026
WASTEWATER PERM INSPECTION ¤80.00 02/06/2026
WASTEWATER PERM REVIEW ¤25.00 02/06/2026
WATER PERMIT REVIEW ¤25.00 02/06/2026
SITE PLAN 30 ¤30.00 02/06/2026
Fees Total Due: ¤0.00 Total Paid: ¤17,990.68