I want to search for...

Permit #2026020301

Permit Details

Status: ISSUED

Parcel Id: 09-12-31-0000-02030-0020
Block: 02030
Subdivision: -
Job Phone: 678-697-0613
Location Address: 60 MEMORIAL MEDICAL PKWY
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 04/28/2026
NOC: RECORDED
Applicant name: BRUCE ROBERT ADAMS
Owner: MEMORIAL HOSPITAL-FLAGLER INC

Address

60 MEMORIAL MEDICAL PKWY

PALM COAST, FL 32164

Lot: 0020
Contracted Stated Job Value: ¤3,303,873.00
Job Description: 1st Floor Locker Rooms and Cath Lab
Type: CN

Contractor

THE ROBINS & MORTON GROUP
Status Location Address Mailing Address State License Number Phone
ACTIVE

423 S KELLER RD

ORLANDO, FL 32810

#200

ORLANDO, FL 32810

CGC1523017 (Exp: 08/31/2026) 407-916-7235

Sub Contractors

DAVID ANTHONY GABEL
Status Location Address State License Number Phone Fax
ACTIVE

231 Jean St.

DAYTONA BEACH, FL 32114

EC13005876 (Exp: 08/31/2026) (386) 255-1418 (386)255-3429
CLIFTON RYAN NASH
Status Location Address State License Number Phone Fax
ACTIVE

PO BOX 98

WILDWOOD, FL 34785

CMC1250561 (Exp: 08/31/2026) 352-748-1454 352-748-2990
CLIFTON RYAN NASH
Status Location Address State License Number Phone Fax
ACTIVE

PO BOX 98

WILDWOOD, FL 34785

CFC1431002 (Exp: 08/31/2026) 352-748-1454 352-748-2990

Inspection History

Type Request Date Result Inspector
PLUMBING 1ST ROUGH
PLUMBING 2ND ROUGH
PLUMBING PRESSURE TEST
PLUMBING FINAL
HVAC ROUGH
HVAC OTHER
HVAC FINAL
ELECTRIC 2ND ROUGH
ELECTRIC FINAL
MEDICAL GAS 1ST ROUGH (UNDERGROUND)
MEDICAL GAS 2ND ROUGH
FRAMING
FIREWALL FRAMING
FIREWALL FINAL
FIREWALL PENETRATIONS
FIREWALL DRYWALL NAILING
ABOVE CEILING
INSULATION
DRYWALL NAILING
BUILDING FINAL
FIRE FINAL
U - UTILITY COMMERCIAL FINAL

Review History

Department Status Date In Date Out
BLD PENDING 06/10/2026
ELEC PENDING 06/10/2026
FI1 PENDING 06/10/2026
MECH PENDING 06/10/2026
BLD HOLD 05/29/2026 06/05/2026
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. All plan pages have to be separated.
ELEC HOLD 05/29/2026 06/05/2026
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. All plan pages have to be separated.
MECH HOLD 05/29/2026 06/05/2026
Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM Plan sheets must be uploaded as separate files
FI1 HOLD 05/29/2026 06/05/2026
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. All plan pages have to be separated.
PLUM COMPLETE 04/21/2026 04/22/2026
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
PLUM HOLD 04/15/2026 04/16/2026
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM COMMENTS BELOW PER THE 2023 FLORIDA BUILDING CODE-BUILDING (FBCB), FLORIDA BUILDING CODE-PLUMBING (FBCP), FLORIDA BUILDING CODE-ACCESSIBILITY (FBCA), FLORIDA STATUTES (F.S.), FLORIDA ADMINISTRATIVE CODE (F.A.C.) AND AUTHORITY HAVING JURISDICTION (A.H.J.). PLAN RE-SUBMITTAL SHALL BE ACCOMPANIED BY A RESPONSE LETTER SIGNED AND SEALED BY THE APPROPRIATE DESIGN PROFESSIONAL(S). ALL PLAN REVISIONS SHALL BE CLOUDED APPROPRIATELY. 1. OK 2. OK 3. Provide copy of plumbing contractor’s medical gas certification. Individual actually performing work on Medical gas systems must also meet specific training requirements per FS 489.1136 (1) (b). Provide copy of current Certificate of Completion for required coursework / training.(NOT UPLOADED)
DSD COMPLETE 03/06/2026 03/09/2026
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
BLD COMPLETE 03/06/2026 03/09/2026
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
MECH COMPLETE 03/06/2026 03/09/2026
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
PLUM HOLD 03/06/2026 03/09/2026
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM COMMENTS BELOW PER THE 2023 FLORIDA BUILDING CODE-BUILDING (FBCB), FLORIDA BUILDING CODE-PLUMBING (FBCP), FLORIDA BUILDING CODE-ACCESSIBILITY (FBCA), FLORIDA STATUTES (F.S.), FLORIDA ADMINISTRATIVE CODE (F.A.C.) AND AUTHORITY HAVING JURISDICTION (A.H.J.). PLAN RE-SUBMITTAL SHALL BE ACCOMPANIED BY A RESPONSE LETTER SIGNED AND SEALED BY THE APPROPRIATE DESIGN PROFESSIONAL(S). ALL PLAN REVISIONS SHALL BE CLOUDED APPROPRIATELY. *NO LETTER SUBMITTED* 1. Add backflow device schedule. List various backflow devices, manufacturer, model and applicable design standard they must conform to for each device type. Section 608. Table 608.1. Backflow preventer required at hose-bibbs, janitor sink, ice-maker, and any other water utilizing appliance connected to the water system including any not shown in the plans (e.g. coffee maker with direct water supply connection). (UNABLE TO LOCATE) 2. OK 3. Provide copy of plumbing contractor’s medical gas certification. Individual actually performing work on Medical gas systems must also meet specific training requirements per FS 489.1136 (1) (b). Provide copy of current Certificate of Completion for required coursework / training.(NOT UPLOADED)
ELEC COMPLETE 03/06/2026 03/16/2026
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
FI1 COMPLETE 03/06/2026 03/16/2026
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
BLD HOLD 02/09/2026 02/18/2026
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM COMMENTS BELOW PER THE 2023 FLORIDA BUILDING CODE-BUILDING (FBCB), FLORIDA BUILDING CODE-ACCESSIBILITY (FBCA), FLORIDA BUILDING CODE-PLUMBING (FBCP), FLORIDA STATUTES (FS), FLORIDA ADMINISTRATIVE CODE (FAC) AND AUTHORITY HAVING JURISDICTION (AHJ). PLAN RE-SUBMITTAL SHALL BE ACCOMPANIED BY A RESPONSE LETTER SIGNED AND SEALED BY THE APPROPRIATE DESIGN PROFESSIONAL(S). ALL PLAN REVISIONS SHALL BE CLOUDED APPROPRIATELY. 1. Structural pages need to have a verifiable digital signature. F.S.471.025 2. All Architectural pages need to be digitally signed and sealed. F.S.471.025, FAC 61G1-16.004 (5) 3. All pages need to have an address. FAC 61G1-16.004 (3), FAC 61G15-23.001 (4) (b) 2. c.
DSD HOLD 02/09/2026 02/10/2026
Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM This is for 60 Memorial Medical not 1 Please correct the address on permit application
ELEC HOLD 02/09/2026 02/18/2026
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Plans need to have address. And permit is for wrong address.
FI1 HOLD 02/09/2026 02/18/2026
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Plans need to have address. And permit is for wrong address.
MECH HOLD 02/09/2026 02/18/2026
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM COMMENTS BELOW PER THE 2023 FLORIDA BUILDING CODE-BUILDING (FBCB), FLORIDA BUILDING CODE- MECHANICAL (FBCM), FLORIDA BUILDING CODE-ENERGY CONSERVATION (FBCEC), FLORIDA STATUTES (FS), FLORIDA ADMINISTRATIVE CODE (FAC) AND AUTHORITY HAVING JURISDICTION (AHJ). PLAN RE-SUBMITTAL SHALL BE ACCOMPANIED BY A RESPONSE LETTER SIGNED AND SEALED BY THE APPROPRIATE DESIGN PROFESSIONAL(S). ALL PLAN REVISIONS SHALL BE CLOUDED APPROPRIATELY. 1. Provide Energy Calculations per C407 FBC Energy Conservation 2023 2. Provide Heatload Calculation per C403.2.1 FBC Energy Conservation 2023 3. Provide Ventilation calculation per Table 403.3.1.1 FBC Mechanical 2023
PLUM HOLD 02/09/2026 02/18/2026
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM COMMENTS BELOW PER THE 2023 FLORIDA BUILDING CODE-BUILDING (FBCB), FLORIDA BUILDING CODE-PLUMBING (FBCP), FLORIDA BUILDING CODE-ACCESSIBILITY (FBCA), FLORIDA STATUTES (F.S.), FLORIDA ADMINISTRATIVE CODE (F.A.C.) AND AUTHORITY HAVING JURISDICTION (A.H.J.). PLAN RE-SUBMITTAL SHALL BE ACCOMPANIED BY A RESPONSE LETTER SIGNED AND SEALED BY THE APPROPRIATE DESIGN PROFESSIONAL(S). ALL PLAN REVISIONS SHALL BE CLOUDED APPROPRIATELY. 1. Add backflow device schedule. List various backflow devices, manufacturer, model and applicable design standard they must conform to for each device type. Section 608. Table 608.1. Backflow preventer required at hose-bibbs, janitor sink, ice-maker, and any other water utilizing appliance connected to the water system including any not shown in the plans (e.g. coffee maker with direct water supply connection). 2. Provide note to indicate all backflow devices are subject to testing by an independent, third party, Florida licensed backflow testing agency and each backflow device will be tested and provided with an approved testing tag at time of installation. 312.10.2 3. Provide copy of plumbing contractor’s medical gas certification. Individual actually performing work on Medical gas systems must also meet specific training requirements per FS 489.1136 (1) (b). Provide copy of current Certificate of Completion for required coursework / training.
UD1 COMPLETE 02/09/2026 02/18/2026
Note: Released By: GREG DEGLER - (386)986-2384 - GDEGLER@PALMCOASTGOV.COM
UD2 COMPLETE 02/09/2026 02/10/2026
Note: Released By: DAN LEMONCELLO - -

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ARTS ¤16,520.00 04/28/2026
ADMINISTRATIVE - COMMERCIAL ¤75.00 04/28/2026
INSPECTION COMMERCIAL ¤23,128.00 04/28/2026
INSPECTION - FIRE COMMERCIAL ¤826.00 04/28/2026
PLAN REVIEW - COMMERCIAL ¤3,799.60 04/28/2026
SURCHARGE FS 533.721 ¤278.29 04/28/2026
SURCHARGE - FS 468.631 ¤417.43 04/28/2026
SITE PLAN 30 ¤30.00 04/28/2026
Fees Total Due: ¤0.00 Total Paid: ¤45,074.32