Permit #2026020563

Permit Details

Status: APPLY

Parcel Id: 07-11-31-7063-RP0J2-0000
Block: RP J2
Subdivision: 2375 - DCI-BELLE TERRE
Job Phone: 501-681-0560
Location Address: 1091 BELLE TERRE BLVD
Type: BC - BUILDING COMMERCIAL
NOC: NO DOCUMENTATION
Applicant name: RYAN A BRADBURY
Owner: JRB-PC LLC

Address

3948 3RD STREET SOUTH

JACKSONVILLE BEACH, FL 32250

Address

SUITE 35

JACKSONVILLE BEACH, FL 32250

Lot: 0000
Contracted Stated Job Value: ¤450,000.00
Job Description: COMMERCIAL BUILDING 7 BREW
Type: CN

Contractor

PRECISION CONSTRUCTION
Status Location Address State License Number Phone
ACTIVE

PO BOX 662

GREENBRIER, AR 72058

CBC1266824 (Exp: 08/31/2026) 501-681-0560

Inspection History

Type Request Date Result Inspector
FORMBOARD SURVEY
GEO TECH CERTIFICATION
PLUMBING 1ST ROUGH
PLUMBING 2ND ROUGH
GRAVITY SEWER
BLD - SEWER TIE IN
WATER SERVICE
PLUMBING FINAL
HVAC ROUGH
HVAC FINAL
ELECTRIC 1ST ROUGH
ELECTRIC 2ND ROUGH
ELECTRIC - EARLY POWER
ELECTRIC FINAL
MONOLITHIC SLAB
FOOTER
LINTEL
FRAMING
ROOF SHEATHING / BRACE / TIE DOWN
ABOVE CEILING
INSULATION
DRYWALL NAILING
STOREFRONT
BUILDING FINAL
FIRE FINAL
EXTERIOR ARCHITECTURAL FEATURES
U - UTILITY COMMERCIAL FINAL

Review History

Department Status Date In Date Out
MECH PENDING 06/04/2026
BLD COMPLETE 06/04/2026 06/11/2026
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
UD2 PENDING 06/04/2026
ELEC COMPLETE 06/04/2026 06/11/2026
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
DSD COMPLETE 06/04/2026 06/04/2026
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
FI1 COMPLETE 06/04/2026 06/11/2026
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
GAS CANCEL 06/04/2026 06/11/2026
UD2 HOLD 04/24/2026 05/04/2026
Note: Held By: DAN LEMONCELLO - - 1) On attachment page M1.1, dated 4/24/2026, must add 2nd page of Palm Coast City Standard details page for plumbing contractor. Plumbing contractor must have all the grease interceptor information before they apply for the separate permit with the correct details. 2) Contact Utility Wastewater Pretreatment Inspector Dan Lemoncello if you need the other page of details. Email @ llemoncello@palmcoastgov.com
MECH HOLD 04/24/2026 05/04/2026
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM COMMENTS BELOW PER THE 2023 FLORIDA BUILDING CODE-BUILDING (FBCB), FLORIDA BUILDING CODE- MECHANICAL (FBCM), FLORIDA BUILDING CODE-ENERGY CONSERVATION (FBCEC), FLORIDA STATUTES (FS), FLORIDA ADMINISTRATIVE CODE (FAC) AND AUTHORITY HAVING JURISDICTION (AHJ). PLAN RE-SUBMITTAL SHALL BE ACCOMPANIED BY A RESPONSE LETTER SIGNED AND SEALED BY THE APPROPRIATE DESIGN PROFESSIONAL(S). ALL PLAN REVISIONS SHALL BE CLOUDED APPROPRIATELY. NO RESPONSE LETTER SUBMITTED REPEAT COMMENT: 1. Provide Heatload Calculation per C403.2.1 FBC Energy Conservation (NOT SUBMITTED) REPEAT COMMENT: 2. Provide manufacturers specs on Ice machine equipment. FBC Energy Conservation (NOT SUBMITTED) REPEAT COMMENT: 3. Provide details for the optional minisplit. FBC 107.2.1(NOT SUBMITTED) 4. OK REPEAT COMMENT: 5. Plan page M3.1 under General Mechanical Notes (#5) rermove referece to IBC 2018. Needs to be 2023 FBC. (NOT SUBMITTED)
PLUM COMPLETE 04/24/2026 05/04/2026
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
BLD HOLD 04/24/2026 05/04/2026
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM COMMENTS BELOW PER THE 2023 FLORIDA BUILDING CODE-BUILDING (FBCB), FLORIDA BUILDING CODE-ACCESSIBILITY (FBCA), FLORIDA BUILDING CODE-PLUMBING (FBCP), FLORIDA STATUTES (FS), FLORIDA ADMINISTRATIVE CODE (FAC) AND AUTHORITY HAVING JURISDICTION (AHJ). PLAN RE-SUBMITTAL SHALL BE ACCOMPANIED BY A RESPONSE LETTER SIGNED AND SEALED BY THE APPROPRIATE DESIGN PROFESSIONAL(S). ALL PLAN REVISIONS SHALL BE CLOUDED APPROPRIATELY. 1. OK REPEAT COMMENT: 2. All architectural plan sheets need to have a digital verifiable signature F.S. 471.025 (ARCHITECTURAL PAGES NEED TO BE DIGITALLY SIGNED AND SEALED. THE MODULAR PLANS ARE GOOD) 3. OK 4. OK REPEAT COMMENT: 5. Plan page A01 in code analysis remove reference to IBC. Needs to say FBC( A01 IS IN THE ARCHTECTURAL PAGES) 6. OK
DSD COMPLETE 03/31/2026 04/01/2026
Note: Released By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM
UD2 HOLD 03/31/2026 04/01/2026
Note: Held By: DAN LEMONCELLO - - 1)A separate permit is required for all grease interceptors. 2)The separate permit must have our City standard details sheets, a details sheet from selected manufacturer and sizing ordered. 3) email Utility Wastewater Pretreatment Inspector, Dan Lemoncello if any questions @ llemoncello@palmcoastgov.com or call (386)286-2011.
BLD HOLD 03/31/2026 04/12/2026
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM COMMENTS BELOW PER THE 2023 FLORIDA BUILDING CODE-BUILDING (FBCB), FLORIDA BUILDING CODE-ACCESSIBILITY (FBCA), FLORIDA BUILDING CODE-PLUMBING (FBCP), FLORIDA STATUTES (FS), FLORIDA ADMINISTRATIVE CODE (FAC) AND AUTHORITY HAVING JURISDICTION (AHJ). PLAN RE-SUBMITTAL SHALL BE ACCOMPANIED BY A RESPONSE LETTER SIGNED AND SEALED BY THE APPROPRIATE DESIGN PROFESSIONAL(S). ALL PLAN REVISIONS SHALL BE CLOUDED APPROPRIATELY. 1. Provide all state approved plans for modular building , including plan index from modular building plans. F.S. 553.37 (1) (a) 2. All architectural plan sheets need to have a digital verifiable signature F.S. 471.025 3. Provide shop drawings for premanufactured canopy, roof guards etc.. or list as deferred submittals 107.2.1 4. Provide live loads and attachment details for guards. 1015.2, 1607.1, 1607.9 5. Plan page A01 in code analysis remove reference to IBC. Needs to say FBC 6. Provide details in ladder for mechanical access room, live loads etc..107.2.1/ 1607.1, Table 1607.1 Further comments may arise after review of manufacturerd building plans
FI1 COMPLETE 03/31/2026 04/13/2026
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
MECH HOLD 03/31/2026 04/12/2026
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM COMMENTS BELOW PER THE 2023 FLORIDA BUILDING CODE-BUILDING (FBCB), FLORIDA BUILDING CODE- MECHANICAL (FBCM), FLORIDA BUILDING CODE-ENERGY CONSERVATION (FBCEC), FLORIDA STATUTES (FS), FLORIDA ADMINISTRATIVE CODE (FAC) AND AUTHORITY HAVING JURISDICTION (AHJ). PLAN RE-SUBMITTAL SHALL BE ACCOMPANIED BY A RESPONSE LETTER SIGNED AND SEALED BY THE APPROPRIATE DESIGN PROFESSIONAL(S). ALL PLAN REVISIONS SHALL BE CLOUDED APPROPRIATELY. 1. Provide Heatload Calculation per C403.2.1 FBC Energy Conservation 2. Provide manufacturers specs on Ice machine equipment. FBC Energy Conservation 3. Provide details for the optional minisplit. FBC 107.2.1 4. Provide note on plans saying condensate from RTU's to route to storm drains per 307.2.1 FBC Mechanical 5. Plan page M3.1 under General Mechanical Notes (#5) rermove referece to IBC 2018. Needs to be 2023 FBC.
PLUM HOLD 03/31/2026 04/12/2026
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM COMMENTS BELOW PER THE 2023 FLORIDA BUILDING CODE-BUILDING (FBCB), FLORIDA BUILDING CODE-PLUMBING (FBCP), FLORIDA BUILDING CODE-ACCESSIBILITY (FBCA), FLORIDA STATUTES (F.S.), FLORIDA ADMINISTRATIVE CODE (F.A.C.) AND AUTHORITY HAVING JURISDICTION (A.H.J.). PLAN RE-SUBMITTAL SHALL BE ACCOMPANIED BY A RESPONSE LETTER SIGNED AND SEALED BY THE APPROPRIATE DESIGN PROFESSIONAL(S). ALL PLAN REVISIONS SHALL BE CLOUDED APPROPRIATELY. 1. Add to plumging fixture and equipment schedule. Show backflow preventer required at hose-bibbs, janitor sink, ice-maker, Espresso machines and any other water utilizing appliance connected to the water system including any not shown in the plans. Section 608. Table 608.1. 2. Provide note to indicate all backflow devices are subject to testing by an independent, third party, Florida licensed backflow testing agency and each backflow device will be tested and provided with an approved testing tag at time of installation. 312.10.2
GAS CANCEL 03/31/2026 04/08/2026
ELEC COMPLETE 03/31/2026 04/13/2026
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
UD1 COMPLETE 03/31/2026 04/15/2026
Note: Released By: GREG DEGLER - (386)986-2384 - GDEGLER@PALMCOASTGOV.COM
ARCHR COMPLETE 02/17/2026 03/03/2026
Note: Released By: RICHARD PICATAGI - (386)986-3760 - RPICATAGI@PALMCOASTGOV.COM
BLD HOLD 02/17/2026 02/18/2026
Note: Held By: LIBBY RAYBURN - - LRAYBURN@PALMCOASTGOV.COM plans cannot be submitted in a group. Must be in single format and file names correct
DSD HOLD 02/17/2026 02/17/2026
Note: Held By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM 1. Upload a stamp approved elevation plans. 2. Upload stamp approved site plan. 3. All the documents with the address of 100 Belle Terre Blvd will need to be updated as this is the incorrect building address. The address for this building is 1091 Belle Terre Blvd.
ELEC HOLD 02/17/2026 02/18/2026
Note: Held By: LIBBY RAYBURN - - LRAYBURN@PALMCOASTGOV.COM plans cannot be submitted in a group. Must be in single format and file names correct
FI1 HOLD 02/17/2026 02/18/2026
Note: Held By: LIBBY RAYBURN - - LRAYBURN@PALMCOASTGOV.COM plans cannot be submitted in a group. Must be in single format and file names correct
GAS HOLD 02/17/2026 02/18/2026
Note: Held By: LIBBY RAYBURN - - LRAYBURN@PALMCOASTGOV.COM plans cannot be submitted in a group. Must be in single format and file names correct
MECH HOLD 02/17/2026 02/18/2026
Note: Held By: LIBBY RAYBURN - - LRAYBURN@PALMCOASTGOV.COM plans cannot be submitted in a group. Must be in single format and file names correct
PLUM HOLD 02/17/2026 02/18/2026
Note: Held By: LIBBY RAYBURN - - LRAYBURN@PALMCOASTGOV.COM plans cannot be submitted in a group. Must be in single format and file names correct
UD1 HOLD 02/17/2026 02/27/2026
Note: Held By: GREG DEGLER - (386)986-2384 - GDEGLER@PALMCOASTGOV.COM See comments from Development Services-Damaris Ramirez
UD2 HOLD 02/17/2026 02/17/2026
Note: Held By: DAN LEMONCELLO - - 1) Contact Utility Wastewater Prtreatment Inspector Dan Lemoncello @ llemoncello@palmcoastgov.com for copy of City standard grease interceptor. 2) Submit peak flow rates for all sinks/drains to calculate interceptor capacity. 3) Must apply for separate permit for grease interceptor approval/pre-delivery and installation and flow/dye test.