Status: INSPECT

Parcel Id: 04-11-30-5571-00000-1760
CONDITIONED SPACE: 1501 sqft
GARAGE: 419 sqft
OPENED PORCH (WITH ROOF) : 72 sqft
OPENED PORCH (WITH ROOF) : 115 sqft
Total Square Footage: 2107 sqft
Subdivision: 2366 - SOMERSET SUBDIVISION PH 2
Job Phone: 904-596-6645
Location Address: 98 TEA OLIVE DR
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 04/15/2026
NOC: RECORDED
Applicant name: MICHAEL T HOLDER
Owner: KB HOME JACKSONVILLE LLC

Address

10475 FORTUNE PARKWAY

JACKSONVILLE, FL 32256

Address

SUITE 100

JACKSONVILLE, FL 32256

Lot: 176
Contracted Stated Job Value: ¤140,000.00
Job Description: SINGLE FAMILY DWELLING
Type: CN

Contractor

KB HOME JACKSONVILLE, LLC
Status Location Address Mailing Address State License Number Phone
ACTIVE

10475 FORTUNE PKWY

JACKSONVILLE, FL 32256

SUITE 100

JACKSONVILLE, FL 32256

CGC1509034 (Exp: 08/31/2026) 904-596-6645

Sub Contractors

BOBBY WAYNE CAMPBELL
Status Location Address State License Number Phone
ACTIVE

117 GUTHRIE ROAD

GREEN COVE SPRINGS, FL 32043

CCC1326752 (Exp: 08/31/2026) 904-200-1600
LARRY WILLIAMS
Status Location Address State License Number Phone
ACTIVE

1750 EMERSON ST

JACKSONVILLE, FL 32207

LI45034 (Exp: 08/31/2026) 904-721-5431
JAMES E LINTON
Status Location Address State License Number Phone
ACTIVE

200 COLLEGE DR

ORANGE PARK, FL 32065

EC0001152 (Exp: 08/31/2026) 904-272-0272
COREY MICHAEL TENNANT
Status Location Address State License Number Phone
ACTIVE

3370 AGRICULTURAL CNETER DR

ST AUGUSTINE, FL 32092

CAC1819063 (Exp: 08/31/2026) 904-829-8898
BENJAMIN MICHAEL RAY
Status Location Address Mailing Address State License Number Phone Fax
ACTIVE

6310 MABLETON PKWY

JACKSONVILLE, FL 32216

SUITE 1000

MABLETON, GA 30126

CFC1428415 (Exp: 08/31/2026) 904-861-5421 904-861-5426

Inspection History

Type Request Date Result Inspector
ROW- PRE-APRON (PRE-POUR) 06/11/2026
Note: 6/10/2026 - PREVIOUS INSPECTION NOTES 06-10-26 TPOLACEK*** THERE IS NOT 6" IN ROW AND THERE IS NOT 4" ABOVE THE ROW. SUB BASE MATERIAL IS NOT COMPACTED AND GRADED.
ROW- PRE-APRON (PRE-POUR) 06/10/2026 Disapproved - NO FEE TPOLACEK
Note: 06-10-26 TPOLACEK*** THERE IS NOT 6" IN ROW AND THERE IS NOT 4" ABOVE THE ROW. SUB BASE MATERIAL IS NOT COMPACTED AND GRADED.
DRYWALL NAILING 06/09/2026 APPROVED JSTEWART
INSULATION 06/04/2026 APPROVED JSTEWART
ALL ROUGH 06/02/2026 APPROVED JSTEWART
Note: 6/1/2026 - PREVIOUS INSPECTION NOTES Repair incomplete. NOTE: Prefab fix truss has been damaged, Metal gussets removed, a repair will be needed for the prefab fix truss. 5/29/2026 - PREVIOUS INSPECTION NOTES Previous Note from Roof sheathing braces and ties, not rectified..... Truss A5 was set backwards, bottom chords were cut and removed, metal gussetts cut and damaged, Webs not to design. Will need a engineered letter submitted for a fix on the structural integrity. Will need to be completed prior to all rough approval. 5/28/2026 - PREVIOUS INSPECTION NOTES 5/21/2026 - PREVIOUS INSPECTION NOTES 1. Missing schedule 80 down pipe at service.NEC 300.5(D)4 2. No water pressure and water service is not connected. FBCR P2503.5 FBCP 603 3. No 5' head on plumbing. FBCR P2503.7 4. Missing nail plates on wires in the Laundry and bedroom next to it.Marked NEC 300.4 5. Wire coming out of the bos in the laundry room is not secured and out of the wall. Marked NEC 334.30 6. Bedroom behind the garage hasa wire that is out of the wall, not safe. Marked NEC 300.4, NEC 334.30 *Note- Gas Rough is Ok. Inspector Notes from Inspection 2467 Inspector Notes from Inspection 2450
ALL ROUGH 06/01/2026 Disapproved - NO FEE JSTEWART
Note: Repair incomplete. NOTE: Prefab fix truss has been damaged, Metal gussets removed, a repair will be needed for the prefab fix truss. 5/29/2026 - PREVIOUS INSPECTION NOTES Previous Note from Roof sheathing braces and ties, not rectified..... Truss A5 was set backwards, bottom chords were cut and removed, metal gussetts cut and damaged, Webs not to design. Will need a engineered letter submitted for a fix on the structural integrity. Will need to be completed prior to all rough approval. 5/28/2026 - PREVIOUS INSPECTION NOTES 5/21/2026 - PREVIOUS INSPECTION NOTES 1. Missing schedule 80 down pipe at service.NEC 300.5(D)4 2. No water pressure and water service is not connected. FBCR P2503.5 FBCP 603 3. No 5' head on plumbing. FBCR P2503.7 4. Missing nail plates on wires in the Laundry and bedroom next to it.Marked NEC 300.4 5. Wire coming out of the bos in the laundry room is not secured and out of the wall. Marked NEC 334.30 6. Bedroom behind the garage hasa wire that is out of the wall, not safe. Marked NEC 300.4, NEC 334.30 *Note- Gas Rough is Ok. Inspector Notes from Inspection 2467 Inspector Notes from Inspection 2450
ALL ROUGH 05/29/2026 Disapproved - NO FEE JSTEWART
Note: Previous Note from Roof sheathing braces and ties, not rectified..... Truss A5 was set backwards, bottom chords were cut and removed, metal gussetts cut and damaged, Webs not to design. Will need a engineered letter submitted for a fix on the structural integrity. Will need to be completed prior to all rough approval. 5/28/2026 - PREVIOUS INSPECTION NOTES 5/21/2026 - PREVIOUS INSPECTION NOTES 1. Missing schedule 80 down pipe at service.NEC 300.5(D)4 2. No water pressure and water service is not connected. FBCR P2503.5 FBCP 603 3. No 5' head on plumbing. FBCR P2503.7 4. Missing nail plates on wires in the Laundry and bedroom next to it.Marked NEC 300.4 5. Wire coming out of the bos in the laundry room is not secured and out of the wall. Marked NEC 334.30 6. Bedroom behind the garage hasa wire that is out of the wall, not safe. Marked NEC 300.4, NEC 334.30 *Note- Gas Rough is Ok. Inspector Notes from Inspection 2467 Inspector Notes from Inspection 2450
ALL ROUGH 05/28/2026 CANCELLED BY APPLICANT JSTEWART
Note: 5/21/2026 - PREVIOUS INSPECTION NOTES 1. Missing schedule 80 down pipe at service.NEC 300.5(D)4 2. No water pressure and water service is not connected. FBCR P2503.5 FBCP 603 3. No 5' head on plumbing. FBCR P2503.7 4. Missing nail plates on wires in the Laundry and bedroom next to it.Marked NEC 300.4 5. Wire coming out of the bos in the laundry room is not secured and out of the wall. Marked NEC 334.30 6. Bedroom behind the garage hasa wire that is out of the wall, not safe. Marked NEC 300.4, NEC 334.30 *Note- Gas Rough is Ok. Inspector Notes from Inspection 2467 Inspector Notes from Inspection 2450
ELECTRIC-TUG 05/28/2026 APPROVED - AS NOTED JSTEWART
Note: Authorize release of email 5/21/2026 - PREVIOUS INSPECTION NOTES 1. Missing schedule 80 down pipe.NEC 300.5(D)4
LATH/BRICK/ WATER BARRIER 05/21/2026 APPROVED HCAMACHO
Note: Inspector Notes from Inspection 2467 Inspector Notes from Inspection 2450
ALL ROUGH 05/21/2026 Disapproved - NO FEE HCAMACHO
Note: 1. Missing schedule 80 down pipe at service.NEC 300.5(D)4 2. No water pressure and water service is not connected. FBCR P2503.5 FBCP 603 3. No 5' head on plumbing. FBCR P2503.7 4. Missing nail plates on wires in the Laundry and bedroom next to it.Marked NEC 300.4 5. Wire coming out of the bos in the laundry room is not secured and out of the wall. Marked NEC 334.30 6. Bedroom behind the garage hasa wire that is out of the wall, not safe. Marked NEC 300.4, NEC 334.30 *Note- Gas Rough is Ok. Inspector Notes from Inspection 2467 Inspector Notes from Inspection 2450
ELECTRIC-TUG 05/21/2026 Disapproved - NO FEE HCAMACHO
Note: 1. Missing schedule 80 down pipe.NEC 300.5(D)4
GRAVITY SEWER TEST 05/20/2026 APPROVED - AS NOTED MCONTRYMAN
Note: Via virtual -Water service line connected to house but no meter installed Inspector Notes from Inspection 2060 Supply not connected
SEWER TIE IN 05/20/2026 APPROVED - AS NOTED MCONTRYMAN
Note: Via virtual -Water service line connected to house but no meter installed Inspector Notes from Inspection 2075 Via virtual -Water service line connected to house but no meter installed Inspector Notes from Inspection 2060 Supply not connected
ROOF VALLEY & METAL 05/15/2026 APPROVED - AS NOTED JSTEWART
Note: Inspector Notes from Inspection 2450
WALL SHEATHING 05/14/2026 APPROVED - AS NOTED JSTEWART
ROOF SHEATHING / BRACES/TIES/DOWN CELL 05/14/2026 APPROVED - AS NOTED JSTEWART
Note: 1. Missing screw tiedowns at front porch trusses to beam. per plan 2. Double stud post needs to be under truss in garage. 3. Replace structural stud in shearwall next to garage to house door, cut for HTT. Maintain 16"OC. 4. Truss A5 was set backwards, bottom chords were cut and removed, metal gussetts cut and damaged, Webs not to design. Will need a engineered letter submitted for a fix on the structural integrity. Will need to be completed prior to all rough approval.
MONOLITHIC SLAB 04/22/2026 APPROVED JSTEWART
Note: Footing depth is at 22".
PLUMBING 1ST ROUGH UNDERGROUND 04/20/2026 APPROVED - AS NOTED KSANDOE
Note: Supply not connected
WATER METER INSTALLATION REQUEST 04/20/2026 APPROVED ISANDERSON
FORMBOARD SURVEY (OFFICE USE ONLY) 04/16/2026 APPROVED RRICKS
ELECTRIC - EARLY POWER
U-CROSS CONNECTION
BLD - BUILDING FINAL
ROW - FINAL APRON (AFTER POUR)
ROW - FINAL INSPECTION
U -UTILITY RESIDENTIAL FINAL

Review History

Department Status Date In Date Out
BLD COMPLETE 06/04/2026 06/05/2026
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
BLD COMPLETE 06/01/2026 06/02/2026
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
SW1 COMPLETE 04/16/2026 04/16/2026
Note: Released By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM
ZON COMPLETE 04/16/2026 04/16/2026
Note: Released By: SCOTT THOMAS - (386)986-3780 - STHOMAS@PALMCOASTGOV.COM
BLD COMPLETE 04/05/2026 04/09/2026
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
CUSVC COMPLETE 04/05/2026 04/09/2026
Note: Released By: HALEIGH HAND - - HHAND@PALMCOASTGOV.COM
ELEC COMPLETE 04/05/2026 04/06/2026
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ENGIN1 COMPLETE 04/05/2026 04/10/2026
Note: Released By: LEVI SALYERDS - (386)986-2575 - LSALYERDS@PALMCOASTGOV.COM
GAS COMPLETE 04/05/2026 04/06/2026
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
LOCATE COMPLETE 04/05/2026 04/07/2026
Note: Released By: IVAN SANDERSON - -
MECH COMPLETE 04/05/2026 04/06/2026
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
SW1 COMPLETE 04/05/2026 04/08/2026
Note: Released By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM
ZON COMPLETE 04/05/2026 04/07/2026
Note: Released By: MICHELLE RAMOS - (386)986-3780 - MRAMOS@PALMCOASTGOV.COM
URB COMPLETE 04/05/2026 04/09/2026
Note: Released By: JOHN BEAUDET - (386)986-2456 - JBEAUDET@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
WATER-METER ¤874.47 04/15/2026
WATER- TURN ON ¤50.00 04/15/2026
ADMINISTRATIVE RESIDENTIAL ¤30.00 04/15/2026
INSPECTION - RESIDENTIAL ¤822.25 04/15/2026
PLAN REVIEW - RESIDENTIAL ¤233.22 04/15/2026
FC IMPACT FEE EMS ¤62.00 04/15/2026
FC IMPACT FEE LAW ENFORCEMENT ¤218.00 04/15/2026
FC IMPACT FEE LIBRARY ¤268.00 04/15/2026
FIRE RES IMPACT FEE 10-25 ¤942.00 04/15/2026
WATER METER W/OUT TAP ¤965.03 04/15/2026
PARKS IMPACT FEE 10-25 ¤3,164.00 04/15/2026
RECLAIM WATER PERMIT INSPECTIO ¤40.00 04/15/2026
RSI DRIVEWAY AFTER POUR ¤16.25 04/15/2026
RSE DRIVE PRE POUR INSPECTION ¤32.50 04/15/2026
RSI FORMBOARD REVIEW ¤16.25 04/15/2026
RSI PLAN REVIEW NEW ¤48.75 04/15/2026
RSI FNL SURVEY/GRADING CERT ¤48.75 04/15/2026
RSI ROW FINAL INSPECTION ¤16.25 04/15/2026
SCHOOL BOARD IMPACT FEE RES ¤5,450.00 04/15/2026
SURCHARGE FS 533.721 ¤10.85 04/15/2026
SURCHARGE - FS 468.631 ¤16.28 04/15/2026
TRANSP RES IMPACT FEE 10-25 ¤5,658.77 04/15/2026
WASTEWATER PERM INSPECTION ¤80.00 04/15/2026
WASTEWATER PERM REVIEW ¤25.00 04/15/2026
SEWER CAPITAL FACILITY ¤3,628.86 04/15/2026
WATER CAPITAL FACILITY FEE ¤3,091.14 04/15/2026
WATER PERMIT REVIEW ¤25.00 04/15/2026
SITE PLAN 30 ¤30.00 04/15/2026
Fees Total Due: ¤0.00 Total Paid: ¤25,863.62