I want to search for...
Permit #2026040686
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7063-00030-0190 |
| Block: 00030 |
| Subdivision: 2174 - SECTION 63-ZEBULAHS TRAIL |
| Job Phone: 386-212-0200 |
| Location Address: 5 ZOFFER CT |
| Type: ME - MECHANICAL |
| Issue Date: 04/16/2026 |
| NOC: Unknown |
| Applicant name: EDWIN D RAINES |
| Owner: GIACCONE AXEL A & RAMON M GIACCONE TIC |
|
Address 718 TURKEY CREEK ALACHUA, FL 32615 |
| Lot: 0190 |
| Contracted Stated Job Value: ¤6,000.00 |
| Job Description: HVAC LIKE FOR LIKE TONNAGE |
| Type: CN |
Contractor
RED, WHITE & BLUE HEATING AND AIR CONDITIONING, IN
| Status | Location Address | State License Number | Phone |
| ACTIVE |
94 S. CAPRI DR ORMOND BEACH, FL 32174 |
CAC1820317 (Exp: 08/31/2026) | 386-212-0200 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 04/23/2026 | CANCELLED BY APPLICANT | WEB |
| Note: 4/21/2026 - PREVIOUS INSPECTION NOTES 4/21/26: A Virtual inspection will be available IF requested at the time of scheduling the re-inspection. If requesting a Virtual Re-inspection, please schedule the re-inspection for the same day that the deficiencies will be corrected and a FaceTime or Google Meet live virtual inspection can be completed. (Pictures are not approved). REQUESTED VIRTUAL INSPECTIONS MUST BE COMPLETED BY 3PM IN ORDER TO BE UPDATED IN THE SYSTEM. 1): 1 of 3 locking caps is not locking. FBC - M1411.8 2). For outdoor condenser disconnect: NEC 350.30(A) LFMC shall be securely fastened in place by an approved means within 12 in. of each box, cabinet, conduit body, or other conduit termination. 3). Please seal exterior wall where lineset exits garage to ODU. FBC EC TABLE R402.4.1.1 | |||
| HVAC FINAL | 04/23/2026 | FINAL APPROVED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 4/23/2026 1:11:26 PM *** New inspection due to canceled inspection 4/21/2026 - PREVIOUS INSPECTION NOTES 4/21/26: A Virtual inspection will be available IF requested at the time of scheduling the re-inspection. If requesting a Virtual Re-inspection, please schedule the re-inspection for the same day that the deficiencies will be corrected and a FaceTime or Google Meet live virtual inspection can be completed. (Pictures are not approved). REQUESTED VIRTUAL INSPECTIONS MUST BE COMPLETED BY 3PM IN ORDER TO BE UPDATED IN THE SYSTEM. 1): 1 of 3 locking caps is not locking. FBC - M1411.8 2). For outdoor condenser disconnect: NEC 350.30(A) LFMC shall be securely fastened in place by an approved means within 12 in. of each box, cabinet, conduit body, or other conduit termination. 3). Please seal exterior wall where lineset exits garage to ODU. FBC EC TABLE R402.4.1.1 | |||
| HVAC FINAL | 04/21/2026 | Disapproved -FEE REQUIRED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 4/21/2026 10:14:18 AM *** 4/21/26: A Virtual inspection will be available IF requested at the time of scheduling the re-inspection. If requesting a Virtual Re-inspection, please schedule the re-inspection for the same day that the deficiencies will be corrected and a FaceTime or Google Meet live virtual inspection can be completed. (Pictures are not approved). REQUESTED VIRTUAL INSPECTIONS MUST BE COMPLETED BY 3PM IN ORDER TO BE UPDATED IN THE SYSTEM. 1): 1 of 3 locking caps is not locking. FBC - M1411.8 2). For outdoor condenser disconnect: NEC 350.30(A) LFMC shall be securely fastened in place by an approved means within 12 in. of each box, cabinet, conduit body, or other conduit termination. 3). Please seal exterior wall where lineset exits garage to ODU. FBC EC TABLE R402.4.1.1 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 04/21/2026 |
| SURCHARGE FS 533.721 | ¤2.00 | 04/16/2026 |
| SURCHARGE - FS 468.631 | ¤2.00 | 04/16/2026 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 04/16/2026 |
| INSPECTION - MECHANICAL | ¤60.00 | 04/16/2026 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤134.00 |