I want to search for...
Permit #2026041031
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-0310-00020-0660 |
| Block: 00020 |
| Subdivision: 31002 - |
| Job Phone: 386-445-5023 |
| Location Address: 77 VERANDA WAY |
| Type: ME - MECHANICAL |
| Issue Date: 04/24/2026 |
| NOC: Unknown |
| Applicant name: MICHAEL FRANK MORELLO |
| Owner: RENTAS MANUEL & MARTHA NIEVES-RENTAS H&W |
|
Address 14 ARENA LAKE CIRCLE PALM COAST, FL 32137 |
| Lot: 0660 |
| Contracted Stated Job Value: ¤6,200.00 |
| Job Description: HVAC LIKE FOR LIKE |
| Type: CN |
Contractor
MIKE MORELLO INC
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
2 HARGROVE GRADE PALM COAST, FL 32164 |
CAC1819466 (Exp: 08/31/2026) | 386-445-5023 | 386-446-4614 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 06/10/2026 | FINAL APPROVED | MCONTRYMAN |
| Note: 6/10/26 Via Virtual 6/9/2026 - PREVIOUS INSPECTION NOTES 5/19/26 Previous note not rectified 2. Chase for ODU lineset needs to be properly sealed -Tape is not a sufficient seal for ac chace 5/19/2026 - PREVIOUS INSPECTION NOTES 5/19/26 1. ODU calls for max of 25amp. 30amp installed in panel NEC 440.4 2. Chase for ODU lineset needs to be properly sealed | |||
| HVAC FINAL | 06/09/2026 | Disapproved -FEE REQUIRED | MCONTRYMAN |
| Note: 5/19/26 Previous note not rectified 2. Chase for ODU lineset needs to be properly sealed -Tape is not a sufficient seal for ac chace 5/19/2026 - PREVIOUS INSPECTION NOTES 5/19/26 1. ODU calls for max of 25amp. 30amp installed in panel NEC 440.4 2. Chase for ODU lineset needs to be properly sealed | |||
| HVAC FINAL | 05/19/2026 | Disapproved - NO FEE | MCONTRYMAN |
| Note: 5/19/26 1. ODU calls for max of 25amp. 30amp installed in panel NEC 440.4 2. Chase for ODU lineset needs to be properly sealed |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 06/10/2026 |
| SURCHARGE FS 533.721 | ¤2.00 | 04/24/2026 |
| SURCHARGE - FS 468.631 | ¤2.00 | 04/24/2026 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 04/24/2026 |
| INSPECTION - MECHANICAL | ¤60.00 | 04/24/2026 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤134.00 |