I want to search for...

Permit #2026041284

Permit Details

Status: INSPECT

Parcel Id: 07-11-31-7037-01520-0190
Block: 01520
Subdivision: 7037 -
Job Phone: 386-445-5023
Location Address: 25 LEE DR
Type: ME - MECHANICAL
Issue Date: 04/30/2026
NOC: Unknown
Applicant name: MICHAEL FRANK MORELLO
Owner: BUONO ROSINA H TRUSTEE

Address

25 LEE DRIVE

PALM COAST, FL 32137

Lot: 0190
Contracted Stated Job Value: ¤12,600.00
Job Description: HVAC LIKE FOR LIKE 4 TON AND 1.5 TON
Type: CN

Contractor

MIKE MORELLO INC
Status Location Address State License Number Phone Fax
ACTIVE

2 HARGROVE GRADE

PALM COAST, FL 32164

CAC1819466 (Exp: 08/31/2026) 386-445-5023 386-446-4614

Inspection History

Type Request Date Result Inspector
HVAC FINAL 05/14/2026 Disapproved - NO FEE JSTEWART
Note: requested virtual inspection, no call. inspector messaged contracting company, Informed I would need to perform the virtual inspection by 4:00p. Please reschedule when work is completed. 5/8/2026 - PREVIOUS INSPECTION NOTES 5/8/26 1. Seal up ceiling penetration for LV line above AH #2 FBC 402.5.1.1 2. ODU #2 has max 15amp. 20 amp breaker installed NEC 440.4 AC 3. AH #1 shows 60amp heat strips. 50amp installed NEC 440.4 AC --Check wire sizes for breaker change at inspection
HVAC FINAL 05/08/2026 Disapproved - NO FEE MCONTRYMAN
Note: 5/8/26 1. Seal up ceiling penetration for LV line above AH #2 FBC 402.5.1.1 2. ODU #2 has max 15amp. 20 amp breaker installed NEC 440.4 AC 3. AH #1 shows 60amp heat strips. 50amp installed NEC 440.4 AC --Check wire sizes for breaker change at inspection
HVAC FINAL
Note: 5/14/2026 - PREVIOUS INSPECTION NOTES requested virtual inspection, no call. inspector messaged contracting company, Informed I would need to perform the virtual inspection by 4:00p. Please reschedule when work is completed. 5/8/2026 - PREVIOUS INSPECTION NOTES 5/8/26 1. Seal up ceiling penetration for LV line above AH #2 FBC 402.5.1.1 2. ODU #2 has max 15amp. 20 amp breaker installed NEC 440.4 AC 3. AH #1 shows 60amp heat strips. 50amp installed NEC 440.4 AC --Check wire sizes for breaker change at inspection

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADMINISTRATIVE RESIDENTIAL ¤30.00 04/30/2026
INSPECTION - MECHANICAL ¤60.00 04/30/2026
SURCHARGE FS 533.721 ¤2.00 04/30/2026
SURCHARGE - FS 468.631 ¤2.00 04/30/2026
Fees Total Due: ¤0.00 Total Paid: ¤94.00