Permit Details
Status: INSPECT
| Parcel Id: 07-11-31-7057-00630-0120 |
| Total Square Footage: 2 sqft |
| Block: 00630 |
| Subdivision: 2123 - SECTION 57-ULYSSES TREES |
| Job Phone: 407-523-0775 |
| Location Address: 376 UNDERWOOD TRL |
| Type: WH - WATER HEATER |
| Issue Date: 05/06/2026 |
| NOC: Unknown |
| Applicant name: CHRISTOPHER ALAN HANMER |
| Owner: BRADLEY GEORGE & PHILAMENA H&W |
|
Address 376 UNDERWOOD TRAIL PALM COAST, FL 32164 |
| Lot: 0120 |
| Contracted Stated Job Value: ¤4,225.00 |
| Job Description: 50 Gallon hybrid water heater changeout |
| Type: CN |
Contractor
FLORIDA ENERGY WATER & AIR
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
6505 EDGEWATER DRIVE ORLANDO, FL 32810 |
CFC023606 (Exp: 08/31/2026) | 407-523-0775 | 407-523-9397 |
Inspection History
| Type | Request Date | Result | Inspector |
| PLUMBING FINAL | 05/15/2026 | Disapproved - NO FEE | CVANSTRAHLEN |
| Note: FBC[A] 110.5-ACCESS FOR INSPECTION - SPECIAL INSTRUCTIONS Knock on door , ring door bell , Not Anwser was given , a grey toyota was park on driveway 5/12/2026 - PREVIOUS INSPECTION NOTES Please fix item before next inspection #1-NEC-250.104(A)(1) General. Metal water piping system(s) installed in or attached to a building or structure shall be bonded to any of the following: (1) Service equipment enclosure (2) Grounded conductor at the service (3) Grounding electrode conductor, if of sufficient size (4) One or more grounding electrodes used, if the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size | |||
| PLUMBING FINAL | 05/12/2026 | Disapproved -FEE REQUIRED | CVANSTRAHLEN |
| Note: Please fix item before next inspection #1-NEC-250.104(A)(1) General. Metal water piping system(s) installed in or attached to a building or structure shall be bonded to any of the following: (1) Service equipment enclosure (2) Grounded conductor at the service (3) Grounding electrode conductor, if of sufficient size (4) One or more grounding electrodes used, if the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size | |||
| PLUMBING FINAL | |||
| Note: 5/15/2026 - PREVIOUS INSPECTION NOTES FBC[A] 110.5-ACCESS FOR INSPECTION - SPECIAL INSTRUCTIONS Knock on door , ring door bell , Not Anwser was given , a grey toyota was park on driveway 5/12/2026 - PREVIOUS INSPECTION NOTES Please fix item before next inspection #1-NEC-250.104(A)(1) General. Metal water piping system(s) installed in or attached to a building or structure shall be bonded to any of the following: (1) Service equipment enclosure (2) Grounded conductor at the service (3) Grounding electrode conductor, if of sufficient size (4) One or more grounding electrodes used, if the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 05/14/2026 |
| SURCHARGE FS 533.721 | ¤2.00 | 05/06/2026 |
| SURCHARGE - FS 468.631 | ¤2.00 | 05/06/2026 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 05/06/2026 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 05/06/2026 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤134.00 |