I want to search for...

Permit #2026050341

Permit Details

Status: APPLY

Parcel Id: 18-11-31-4961-00000-0010
Total Square Footage: 997 sqft
Block: 00000
Subdivision: 1156 - PALM HARBOR COM. CENTER II
Job Phone: 386-316-8200
Location Address: 7 OLD KINGS RD N
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
NOC: NO DOCUMENTATION
Applicant name: STEVEN BRIAN COHEN
Owner: OLD KINGS COMMONS ONE LLC & OLD KINGS COMMONS TWO

Address

2233-B E. FT. KING STREET

OCALA, FL 34471

Lot: 0010
Contracted Stated Job Value: ¤20,000.00
Job Description: Unit 4 Interior Renovations Hill Chiropractic
Type: CN

Contractor

CGC & ASSOCIATES
Status Location Address State License Number Phone Fax
ACTIVE

299 S TYMBER CREEK RD

ORMOND BEACH, FL 32174

CGC045368 (Exp: 08/31/2026) 386-316-8200 386-671-6297

Sub Contractors

JONATHAN G GASSETT
Status Location Address State License Number Phone
ACTIVE

1345 N US HWY 1

ORMOND BEACH, FL 32174

EC13008772 (Exp: 08/31/2026) 386-672-8494
ALAN NORMAN
Status Location Address State License Number Phone
ACTIVE

59 MAYFIELD CIR

ORMOND BEACH, FL 32174

CFC1431949 (Exp: 08/31/2026) 386-852-2526

Inspection History

Type Request Date Result Inspector
PLUMBING 1ST ROUGH
PLUMBING 2ND ROUGH
PLUMBING FINAL
HVAC ROUGH
HVAC FINAL
ELECTRIC 2ND ROUGH
ELECTRIC FINAL
MONOLITHIC SLAB
FRAMING
FIREWALL FINAL
FIREWALL PENETRATIONS
ABOVE CEILING
INSULATION
BUILDING FINAL
FIRE FINAL
U - UTILITY COMMERCIAL FINAL

Review History

Department Status Date In Date Out
FI1 HOLD 06/10/2026 06/15/2026
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Plan is cut off. not a full page.
MECH PENDING 06/10/2026
PLUM PENDING 06/10/2026
BLD PENDING 06/10/2026
ELEC HOLD 06/10/2026 06/15/2026
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Electrical plan is cut off cant see any of the new changes. 1. Need to know what type of X-Ray machine is going to be installed. NEC 2020 660.2 2. Show what type of connection will be installed. NEC 2020 660.4 3. Show where the disconnect is located for the X-Ray machine. NEC 2020 660.5 4. Show location of panel.
BLD HOLD 05/10/2026 05/12/2026
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM COMMENTS BELOW PER THE 2023 FLORIDA BUILDING CODE-BUILDING (FBCB), FLORIDA BUILDING CODE-ACCESSIBILITY (FBCA), FLORIDA BUILDING CODE-PLUMBING (FBCP), FLORIDA STATUTES (FS), FLORIDA ADMINISTRATIVE CODE (FAC) AND AUTHORITY HAVING JURISDICTION (AHJ). PLAN RE-SUBMITTAL SHALL BE ACCOMPANIED BY A RESPONSE LETTER SIGNED AND SEALED BY THE APPROPRIATE DESIGN PROFESSIONAL(S). ALL PLAN REVISIONS SHALL BE CLOUDED APPROPRIATELY. 1. Provide manufacturers specs on Xray machine showing it meets the exception in FBCB 465.2.1 High Radiation Area and is not governed by the State of Florida 2. Provide bathroom finish in accordance with 1210.2.2. Epoxy paint not allowed
DSD COMPLETE 05/10/2026 05/11/2026
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
ELEC HOLD 05/10/2026 05/11/2026
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Need to know what type of X-Ray machine is going to be installed. NEC 2020 660.2 2. Show what type of connection will be installed. NEC 2020 660.4 3. Show where the disconnect is located for the X-Ray machine. NEC 2020 660.5 4. Show location of panel.
FI1 HOLD 05/10/2026 05/11/2026
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Show location, type and size of fire extinguishers. FFPC 8th edition 39.3.5 2. Place note on Life Safety plan that Fire sprinkler and Fire alarm will be on a separate permit.
PLUM HOLD 05/10/2026 05/12/2026
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM COMMENTS BELOW PER THE 2023 FLORIDA BUILDING CODE-BUILDING (FBCB), FLORIDA BUILDING CODE-PLUMBING (FBCP), FLORIDA BUILDING CODE-ACCESSIBILITY (FBCA), FLORIDA STATUTES (F.S.), FLORIDA ADMINISTRATIVE CODE (F.A.C.) AND AUTHORITY HAVING JURISDICTION (A.H.J.). PLAN RE-SUBMITTAL SHALL BE ACCOMPANIED BY A RESPONSE LETTER SIGNED AND SEALED BY THE APPROPRIATE DESIGN PROFESSIONAL(S). ALL PLAN REVISIONS SHALL BE CLOUDED APPROPRIATELY. 1. Provide water supply sizing of all plumbing fixtures 604.5/Table 604.5 FBCP 2. Project is a shown as a "B" occupancy, but the minimum plumbing requirements shows mercantile in code analysis. 107.2.1 3. Provide location of service sink listed in plumbing requirements. 107.2.1
MECH HOLD 05/10/2026 05/12/2026
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Do the walls in the Xray room go to the ceiling? If so provide return air out of room on duct layout
ELEC PENDING
FI1 PENDING