I want to search for...

Permit #2026050479

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7037-00040-0010
Block: 00040
Subdivision: 7037 -
Job Phone: 941-932-8560
Location Address: 13 LUTHER DR
Type: EL - ELECTRICAL
Issue Date: 05/12/2026
NOC: RECORDED
Applicant name: BRUCE HOWARD FORT JR
Owner: HAND KEVIN E & HALEIGH S H&W

Address

13 LUTHER DRIVE

PALM COAST, FL 32137

Lot: 0010
Contracted Stated Job Value: ¤7,081.25
Job Description: EMERGENCY: Add disconnect, replace panel and replace wires
Type: CN

Contractor

MISTER SPARKY
Status Location Address State License Number Phone
ACTIVE

624 27TH STREET CIRCLE E

,

EC13008384 (Exp: 08/31/2026) 941-932-8560

Inspection History

Type Request Date Result Inspector
ELECTRIC FINAL 06/03/2026 FINAL APPROVED JSTEWART
Note: 5/13/2026 - PREVIOUS INSPECTION NOTES Not ready incomplete. 1. All wires from attic to sub panel need to be secured with 12" of sub panel. NEC 334.30 2. Protection above sub panel for all wires. (conduit, wood framed chase with drywall, etc.) NEC 334.15(B) / NEC 300.4 3. Please seal interior and exterior conduit penetration of CMU wall. 4. Holes In drywall for the wires penetrating the garage ceiling, please seal the annular space with fire foam. R402.4.1 5. Dead front at main disconnect needs a screw to secure the panel. NEC 312.10
ELECTRIC FINAL 05/13/2026 Disapproved - NO FEE JSTEWART
Note: Not ready incomplete. 1. All wires from attic to sub panel need to be secured with 12" of sub panel. NEC 334.30 2. Protection above sub panel for all wires. (conduit, wood framed chase with drywall, etc.) NEC 334.15(B) / NEC 300.4 3. Please seal interior and exterior conduit penetration of CMU wall. 4. Holes In drywall for the wires penetrating the garage ceiling, please seal the annular space with fire foam. R402.4.1 5. Dead front at main disconnect needs a screw to secure the panel. NEC 312.10

Review History

Department Status Date In Date Out
ELEC COMPLETE 05/12/2026 05/12/2026
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADMINISTRATIVE RESIDENTIAL ¤30.00 05/12/2026
INSPECTION- ELECTRICAL ¤60.00 05/12/2026
PLAN REVIEW - MISC 32.50 ¤32.50 05/12/2026
SURCHARGE FS 533.721 ¤2.00 05/12/2026
SURCHARGE - FS 468.631 ¤2.00 05/12/2026
Fees Total Due: ¤0.00 Total Paid: ¤126.50