I want to search for...

Permit #2026030338

Permit Details

Status: INSPECT

Parcel Id: 07-11-31-7024-00330-0070
Block: 00330
Subdivision: -
Job Phone: 386-795-9854
Location Address: 24 PRETORIA LN
Type: ME - MECHANICAL
Issue Date: 03/20/2026
NOC: Unknown
Applicant name: DAVID JOSHUA COX
Owner: SOTO ANSELMO ALONSO & KAREN BARRETO PUCA H&W

Address

24 PRETORIA LANE

PALM COAST, FL 32164

Lot: 0070
Contracted Stated Job Value: ¤11,619.07
Job Description: HVAC CO LIKE FOR LIKE
Type: CN

Contractor

ONE HOUR AIR CONDITIONING & HEATING
Status Location Address State License Number Phone
ACTIVE

3000 S. RIDGEWOOD AVE # B

SOUTH DAYTONA, FL 32119

CAC1817215 (Exp: 08/31/2026) 386-262-1247

Inspection History

Type Request Date Result Inspector
HVAC FINAL 05/07/2026 Disapproved -FEE REQUIRED RSIMS
Note: *** NOTES ADDED BY RSIMS 5/7/2026 11:39:23 AM *** 5/7/26: 1). Breaker for AHU does not match the required amperage for the unit. (Min. - 30.8amps / Max. - 35amps --- 30amp installed). NEC 440.4 2). Missing the Notice to Homeowner sticker on electrical box stating that the AHU is located in the attic as required. FBC-M1401.1 > FBEC-R403.3.6 -- Please see code for full requirements. NOTE: A Virtual inspection will be available IF requested at the time of scheduling the re-inspection. If requesting a Virtual Re-inspection, please schedule the re-inspection for the same day that the deficiencies will be corrected and a FaceTime or Google Meet live virtual inspection can be completed. (Pictures are not approved). REQUESTED VIRTUAL INSPECTIONS MUST BE COMPLETED BY 3PM IN ORDER TO BE UPDATED IN THE SYSTEM.
HVAC FINAL
Note: 5/7/2026 - PREVIOUS INSPECTION NOTES 5/7/26: 1). Breaker for AHU does not match the required amperage for the unit. (Min. - 30.8amps / Max. - 35amps --- 30amp installed). NEC 440.4 2). Missing the Notice to Homeowner sticker on electrical box stating that the AHU is located in the attic as required. FBC-M1401.1 > FBEC-R403.3.6 -- Please see code for full requirements. NOTE: A Virtual inspection will be available IF requested at the time of scheduling the re-inspection. If requesting a Virtual Re-inspection, please schedule the re-inspection for the same day that the deficiencies will be corrected and a FaceTime or Google Meet live virtual inspection can be completed. (Pictures are not approved). REQUESTED VIRTUAL INSPECTIONS MUST BE COMPLETED BY 3PM IN ORDER TO BE UPDATED IN THE SYSTEM.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADMINISTRATIVE RESIDENTIAL ¤30.00 03/20/2026
INSPECTION - MECHANICAL ¤60.00 03/20/2026
SURCHARGE FS 533.721 ¤2.00 03/20/2026
SURCHARGE - FS 468.631 ¤2.00 03/20/2026
REINSPECTION RESIDENTIAL ¤40.00
Fees Total Due: ¤40.00 Total Paid: ¤94.00